![background image](http://html1.mh-extra.com/html/ifm/ac2488/ac2488_operating-instructions-manual_3883299004.webp)
4
4.1 Pin connection
M12 connector
1: AS-i +
3: AS-i -
Input M8
1: Sensor
3: Sensor supply -
4: Data input
Parameter bit
Designation
Description
P1
Periphery fault
1 periphery fault indication active
0 periphery fault indication not active
In the AS-i network the AC2489 module functions like 2 independent A/B slaves.
5 Addressing
► Addressing the unit via the M12 connector (AS-i); the address is set to 0 at the
factory.
AC1154 addressing unit
Wiring of the addressing socket
5
1
3
4
2
1: AS-i + / 2: TTL → / 3: AS-i -
4: TTL ← / 5: + 5 V
5.1 Addressing the AC2489 module
In the factory setting, initially only the first slave gives a signal on address 0. It can
be addressed to any address between 1A...31B.
If this slave is addressed, the second slave with the address 0 appears
automatically in the display. Now this slave can be addressed to any address
between 1A...31B.
Both slaves can be assigned any A/B addresses (e.g. 3A/6A or 9A/25B....).
No address can be assigned twice (e.g. 3A/3A or 9B/9B).
If a slave with the ID code "A" (extended address mode possible) is used in
combination with a master of the 1st generation (version 2.0),
- the parameter P3 must be 1 and the output bit D3 must be 0.* The output bit
D3 must not be used.
- an address between 1A and 31A must be assigned to this slave.
* default setting