Adjustable parameters
25
ENGLISH
Analogue start point
Measured value at which 4 mA (20 mA if OU2 = Ineg) is provided.
Analogue end point
Measured value at which 20 mA (4 mA if OU2 = Ineg) is provided.
Minimum distance between ASP and AEP: 50°C / 90°F.
Min-Max memory for system temperature
• HI: displays the highest measured temperature.
• LO: displays the lowest measured temperature.
Erase the memory: Click on the respective reset button.
It is recommended to erase the memory as soon as the unit
starts working under normal operating conditions.
ASP
Configuration of the analogue output
- I = current output 4 ... 20 mA.
- Ineg = current output 20 ... 4 mA.
OU2
AEP
HI
LO
Drift warning threshold
Value at which OUT1 provides a warning message according to
the configuration.
drW
Drift alarm threshold
Value at which OUT1 provides an alarm message according to
the configuration.
• Setting range (drW / drA): 0.2 ... 5°C / 0.4 ... 9°F,
• in steps of 0.05°C / 0.1°F.
drA
Technical information / Functioning / Parameters
in steps of
ASP
Setting range:
AEP
°C
0.05
-25 ... +100
+40 ... +150
-13 ... +212 +104 ... +302
°F
0.1