With the parameter "Lower end of analog output" (
ASP
) you can
select the measuring value for which the output signal is 4 mA or
0V. With the parameter "Upper end of analog output" (
AEP
) you
can select the measuring value for which the output signal is 20
mA or 10 V.
Minimum distance between ASP and AEP = 40 % of the final value of
the measuring range.
The output signal is between 0 and 10V in the set measuring range.
It is also indicated:
Flow above the measuring range: output signal > 10V.
The output signal is between 4 and 20mA in the set measuring range.
It is also indicated:
Flow above the measuring range: output signal > 20mA..
Page 28
Scaling the measuring
range
(analog output)
Voltage output
0 ... 10V
Current output
4 ... 20mA
Technical information / Functioning / Parameters
U [V]
Q
10
MEW
0
U [V]
Q
10
AEP
ASP
0
MEW
factory setting
measuring range scaled
MEW = value of measuring range
I [mA]
Q
4
20
MEW
0
I [mA]
Q
4
20
AEP
ASP
0
MEW
factory setting
measuring range scaled
MEW = value of measuring range