Menu structure
→
fold-out page
Page 24
Adjustable
parameters
Technical information / Functioning / Parameters
Switch-on point 1 / 2:
Upper limit value at which the output changes its switching
status. Setting range(in brackets: in steps of):
Switch-off point 1 / 2:
Lower limit value at which the output changes its switching
status. Setting range(in brackets: in steps of):
SP2 is active only if
OU2
=
Hno, Hnc, Fno
or
Fnc
rPx is always lower than SPx. The unit only accepts values which are lower than SPx.
Changing the switch-on point also changes the switch-off point (the hysteresis remains
constant).
If the hysteresis is higher than the new switch point, it is automatically reduced. rPx is set
to the minimum setting value (0.0).
rP2 is active only if
OU2
=
Hno, Hnc, Fno
or
Fnc
litre / min.
0.1 ... 12 (0.1)
0.03 ... 3.17 (0.01)
0.05 ... 6.34 (0.01)
0.1 ... 12.7 (0.1)
6 ... 720 (1)
10 ... 1 440 (10)
20 ... 2 880 (10)
2 ... 190 (1)
3 ... 380 (1)
6 ... 763 (1)
0.01 ... 0.72 (0.01)
0.01 ... 1.44 (0.01)
0.02 ... 2.88 (0.01)
15
19
24
0.2 ... 24 (0.1)
0.4 ... 48 (0.1)
gallons / min.
litre / hour
1)
gallons / hour
cubic metre /hour
for nominal
diameter
litre / min.
0.0 ... 11.9 (0.1)
0.00 ... 3.14 (0.01)
0.00 ... 6.29 (0.01)
0.0 ... 12.6 (0.1)
0 ... 714 (1)
0 ... 1 430 (10)
0 ... 2 860 (10)
0 ... 188 (1)
0 ... 377 (1)
0 ... 757 (1)
0.00 ... 0.71 (0.01)
0.00 ... 1.43 (0.01)
0.00 ... 2.86 (0.01)
15
19
24
0.0 ... 23.8 (0.1)
0.0 ... 47.6 (0.1)
gallons/ min
litre / hour
1)
gallons / hour
cubic metre /hour
for nominal
diameter
Configuration of output 1
4 switching functions can be set:
-
Hno
= hysteresis / normally open
-
Hnc
= hysteresis / normally closed
-
Fno
= window function / normally open
-
Fnc
= window function / normally closed
Configuration of output 2
4 switching functions and 2 analog signals can be set:
-
Hno
= hysteresis / normally open
-
Hnc
= hysteresis / normally closed
-
Fno
= window function / normally open
-
Fnc
= window function / normally closed
-
I
= analog output 4 ... 20 mA
-
U
= analog output 0 ... 10 V
1)
For
nominal diameter 19 and 24,
1/10 of the LPH value is displayed.
The displayed value must be multiplied by factor 10.
Example:
displayed value = 98
;
real value
= 98 * 10 =
980 LPH