CR7200
Characteristics of the outputs (per control unit)
Outputs
(B
H
, PWM, PWM
I
)
■
Semiconductor outputs, with diagnostic capability
-- %QX0.00...03
positive switching (high side), short-circuit and overload protected
▲
%QX0.04...07
switching voltage
10...32 V DC
can be configured as ...
switching current
max. 4 A
output frequency
max. 100 Hz (depending on the load)
■
PWM outputs, diagnosis via current feedback
PWM frequency
max. 250 Hz
mark-to-space ratio
1...99 %
resolution
depends on the PWM frequency
load current
max. 4 A
■
Current-controlled outputs, diagnosis via current feedback
load current
0,1...4 A
load resistance
min. 3
Ω
(at U
B
= 12 V DC)
min. 6
Ω
(at U
B
= 24 V DC)
setting resolution
1 mA
control resolution
5 mA
accuracy
± 2% FS
Outputs
(B
H
)
■
Semiconductor outputs, with diagnostic capability
-- %QX0.08...15
positive switching (high side), short-circuit and overload protected
can be configured as ...
switching voltage
10...32 V DC
switching current
max. 2 A
output frequency
max. 100 Hz (depending on the load)
Outputs
(B
H
, PWM)
■
Semiconductor outputs, with diagnostic capability
▲
%QX1.00, 03, 04, 07
positive switching (high side), short-circuit and overload protected
can be configured as ...
switching voltage
10...32 V DC
switching current
max. 4 A
output frequency
max. 100 Hz (depending on the load)
■
PWM outputs
PWM frequency
max. 250 Hz
pulse ratio
1...99 %
resolution
depends on the PWM frequency
load current
max. 4 A
Outputs
(B
L/H*
)
■
Semiconductor outputs, with diagnostic capability
▲
%QX1.01, 02, 05, 06
positive/negative switching (high/low side), short-circuit and overload protected
can be configured as ...
switching voltage
10...32 V DC
switching current
max. 4 A
output frequency
max. 100 Hz (depending on the load)
*) only High Side outputs safety-related
Overload protection
max. 5 minutes (at 100%)
(valid for all outputs)
Internal relay outputs
Normally open contacts in series to 2 groups of 12 semiconductor outputs.
for the additional deactivation
Sustained forcing by means of hardware and additional controlling
of the outputs
by means of user program.
The relays must always be switched without load!
total current
max. 12 A per group
switching current
0.1...15 A
overload current
20 A
number of operating cycles
≥
10
6
(without load)
switching-time constant
≤
3 ms
Output Error
■
Semiconductor output, positive switching (high side)
switching voltage
10...32 V DC
switching current
max. 100 mA
overload current
0.5 A
switching function
OFF (0 V) in case of an error
ifm electronic gmbh • Teichstraße 4 • 45 127 Essen
16.10.2006
We reserve the right to make technical alterations without prior notice.
CR7200 / page 4
Abbreviations
▲
= safety-related
--
= not safety-related
A
= analogue
B
H
= binary High Side
B
L
= binary Low Side
FRQ/CYL = frequency inputs
I
H
= pulse High Side
I
L
= pulse Low Side
PWM
= pulse width modulation
PWM
I
= current-controlled output
%IW...
= IEC address for analogue input
%IX...
= IEC address for binary input
%QX...
= IEC address for binary output
Summary of Contents for CR7200
Page 49: ...Anhang Appendix Annexe SAFETYCONTROLLER CR7200 PAGE 49 DEUTSCH ENGLISH FRANÇAIS ...
Page 50: ...SAFETYCONTROLLER CR7200 PAGE 50 ...
Page 51: ...SAFETYCONTROLLER CR7200 PAGE 51 ...
Page 52: ...SAFETYCONTROLLER CR7200 PAGE 52 ...
Page 53: ...SAFETYCONTROLLER CR7200 PAGE 53 ...
Page 54: ...Notizen Notes SAFETYCONTROLLER CR7200 PAGE 54 ...