CR7200
Characteristics of the inputs (per control unit)
Digital/analogue inputs
(B
L
, A)
■
Voltage inputs
▲
%IW03...10
input voltage
0...10/32 V
▲
%IX0.00...07
resolution
12 bits
can be configured as ...
precision
± 1.0% FS
input resistance
50/30 k
Ω
input frequency
50 Hz
■
Current inputs
input current
0/4...20 mA
resolution
12 bits
precision
± 1.0% FS
input resistance
400
Ω
input frequency
50 Hz
■
Digital inputs for positive sensor signals
switch-on level
0.7 U
B
switch-off level
0.4 U
B
input resistance
30 k
Ω
input frequency
50 Hz
Digital inputs
(B
L
)
■
Digital inputs for positive sensor signals
-- %IX0.08...11
switch-on level
0.43...0.73 U
B
can be configured as ...
switch-off level
0.29 U
B
input resistance
3.21 k
Ω
input frequency
50 Hz
Digital inputs
(B
L
, I
L
)
■
Digital inputs for positive sensor signals
▲
%IX0.12...15
switch-on level
0.7 U
B
can be configured as ...
switch-off level
0.4 U
B
input resistance
2.86 k
Ω
input frequency
50 Hz
■
Frequency inputs for positive sensor signals
evaluation with integrated comparator
switch-on level
0.43...0.73 U
B
switch-off level
0.29 U
B
input resistance
2.86 k
Ω
input frequency
max. 50 kHz
Digital inputs
(B
L
, I
L
)
■
Digital inputs for positive sensor signals
▲
%IX1.04...07
switch-on level
0.7 U
B
can be configured as ...
switch-off level
0.4 U
B
input resistance
3.21 k
Ω
input frequency
50 Hz
■
Frequency inputs for positive sensor signals
evaluation with integrated comparator
switch-on level
0.43...0.73 U
B
switch-off level
0.29 U
B
input resistance
3.21 k
Ω
input frequency
max. 1 kHz
Digital inputs
(B
L/H
)
■
Digital inputs for positive/negative sensor signals
-- %IX1.08...15
switch-on level
0.7 U
B
can be configured as ...
switch-off level
0.4 U
B
input resistance
3.21 k
Ω
input frequency
50 Hz
Test input
The test input must be active when e.g. software is to be downloaded in the controller
(pin 24 to VBB
S
, 10...32 V DC).
Safety-related outputs (MODE byte OUT_Safety) cannot be used with the test input
active. Deactivate the test input and carry out a reset to make them available again.
(Reset = switching on / off of the controller)
During operation of the machine the test input must be connected to GND.
input resistance
3.21 k
Ω
Observe the special notes in the documentation "Supplement to the system manual,
SafetyController R360".
ifm electronic gmbh • Teichstraße 4 • 45 127 Essen
16.10.2006
We reserve the right to make technical alterations without prior notice.
CR7200 / page 3
Summary of Contents for CR7200
Page 49: ...Anhang Appendix Annexe SAFETYCONTROLLER CR7200 PAGE 49 DEUTSCH ENGLISH FRANÇAIS ...
Page 50: ...SAFETYCONTROLLER CR7200 PAGE 50 ...
Page 51: ...SAFETYCONTROLLER CR7200 PAGE 51 ...
Page 52: ...SAFETYCONTROLLER CR7200 PAGE 52 ...
Page 53: ...SAFETYCONTROLLER CR7200 PAGE 53 ...
Page 54: ...Notizen Notes SAFETYCONTROLLER CR7200 PAGE 54 ...