Electrical connection
Ethernet ports
>
6.2
Ethernet ports
22683
► Connect the unit via the M12 socket X21 and/or X22 with the
PROFINET network (e.g. PROFINET PLC, additional
PROFINET device)
Tightening torque: 0.6...0.8 Nm
► Connect the unit via the M12 socket X21 and/or X22 to the
industrial Ethernet network (e.g. laptop/PC with installed
parameter setting software LR DEVICE, laptop/PC with
installed monitoring software LR SMARTOBSERVER)
Tightening torque: 0.6...0.8 Nm
► For the connection, use M12 connectors with protection rating
IP 65 / IP 66 / IP 67 or higher (
→
Accessories
(
)).
► Cover the unused sockets with M12 protective caps (art no.
E73004).
Tightening torque 0.6...0.8 Nm
>
6.3
IO-Link ports
22684
Ports X01...X04: For use as IO-Link port class A:
► Connect the connector of the IO-Link devices with the M12 sockets
X01 ... X04.
Tightening torque: 0.6...0.8 Nm
Maximum cable length per IO-Link interface: 20 m
► For the connection, use M12 connectors with protection rating IP 65
/ IP 66 / IP 67 or higher (
→
Accessories
(
Ports X01...X04: For use as IO-Link port class B:
► Connect the connector of the IO-Link devices via the adapter with
the M12 sockets X01 ... X04.
Tightening torque: 0.6...0.8 Nm
► To connect the devices, use M12 connectors with protection rating
IP 65 / IP 66 / IP 67 or higher (
→
Accessories
(
)).
► Cover the unused sockets with M12 protective caps (art no.
E73004).
Tightening torque 0.6...0.8 Nm