C O N F I G U R A T I O N & O P E R A T I O N
List of alarms
In case of alarm, the status icon located at the right hand side in the bo om footer of the screen
can be either:
Alarm level 1, cri cal alarm will stop opera on of IER, if latched will need manual reset by
service technician.
Alarm level 2, non-cri cal alarm will not stop opera on of IER, auto reset as soon as default is
over.
Alarm
Level Descrip on
Service needed
2
Servicing the cylinder is required
latched if set as is by installer
Air Flow error
1
No air flow in the duct
Hi Rh% in duct detected
1
A duct Hi limit RH% sensor or switch is installed and has
detected High humidity.
Enable Switch
1
Enable switch is off
High temperature Switch
1
latched
Hi limit safety switch located on top of the cylinder is
open
Water level sensor def
1
Water level sensor is defec ve
Water level sensor error
1
Water level detected is abnormal
Water level too high
1
Water level is higher than expected
Water level too low
2
Water level is lower than expected
Water Temp. Sensor def
1
latched Water temperature sensor is defec ve
Water Temp. Sensor error 1
Water temperature measured is abnormal
Foam detected
1
Foam is detected in the cylinder
latched in case of repe on
Water inlet Low Flow
2
Fill or refill of cylinder is longer than expected
Water Feed Error
1
No water is supplied
Drain pump error
1
Drain pump is not able to empty cylinder
Unit not hea ng
2
IER not hea ng water
Electric supply
2
Low power
No control Connected
2
No signal received
Communica on Status
2
Loss of communica on between board computer and
Main controller
46