I N S T A L L A T I O N
Installation – step 3
Drain installation
Water drained specification:
Drained water maximum temperature: 140°F [60°C] (
when supplied with cold water supply)
Drained water flow rate: 6.6 GPM [25 l/min]
Drain outlet dimension:
IER04 to IER31
: (1x)1-1/4in [32mm]
IER24. IER34, IER44 & IER62
: (2x)1-1/4in [32mm]
Drain volume for full cylinder drain:
IER04 to 09
: 5.5Gal [21L]
IER12, IER17, IER22, IER31
: 12Gal [46L]
IER24, 34, 44 & 62
: 24Gal [86.5L]
IER humidifier
Drain
Connec on sleeve 1-1/4in [32mm]
(by others)
Slope minimum 5°
P trap
Open drain offset from IER
1-1/2in [40mm] minimum
2 collars
(by others)
18in [45cm]
minimum
18in [45cm]
minimum
Figure 14, water drain connec on (single module)
Connec on sleeve 1-1/4in [32mm]
(supplied)
2 collars
(by others)
IER module 2
Drain
Slope minimum 5°
P trap
Open drain offset from IER
1-1/2in [40mm] minimum
18in [45cm]
minimum
18in [45cm]
minimum
IER module 1
Figure 15, water drain connec on, 2 modules, model IER24, 34, 44 & 62
19