Wiegand formats
If there is need to change your Wiegand format from 26 bit , use the chart below
92 #
Options #
Value # * *
1. –Wiegand format
1 – 8 ( Defaults to 1 = 26 Bit )
2. –Inter Pulse spacing
1 – 225 ( Defaults to 32 = 640
usecs)
3. –Pulse width
1 – 255 ( Defaults to 8 = 160
usecs)
93 #
ID type #
ID Value # * *
0 – Site ID
0 – 999 ( Deafults to 0 )
1 – Group ID
0 – 999 Defaults to 0 )
Wiegand Formats
Format Frame
size
PIN’s
Sites
Groups
1 26
Bit
65536
256
N/A
2 28
Bit
32768
256
N/A
3 29
Bit
524288
256
N/A
4 30
Bit
65536
256
16
5 31
Bit
65336
256
32
6 32
Bit
65536
2048
64
7 36
Bit
1048576
256
N/A
Self Test:
After installation it is recommended that you
perform the self test mode. While the unit is powered
up, enter the following on the SSiLW keypad:
7890#123456 * . If all 12 key presses have been
verified, the keypad will enter self test mode. The
LED’s will alternate three times and the sounder will
beep three times followed by a flickering yellow LED.
Press any key to return to normal operation.
System Defaults:
The SS-iLW series keypad is designed for easy
installation in a minimum amount of time. The
following values have been factory programmed.
Front end designation
HFE
( Hub front end)
SS-iLW Keypad program code
6789
Audible keypress fedback
on
Visual keypress feedback
on
Log event recording
on
If it is necessary to change any of these defaults,
please refer to your programming options chart after
you have familiarized yourself with the programming
sections.