Troubleshooting
9
p.59
☞ All iMDC-RIM’s output status LEDs are lit up
Cause
It may be caused from operating disconnection mode or poor networking
condition or wrong iMDC network setting.
Solution
1. If it occurs at the first boot after installation of iMDC
Once power is supplied after the first installment of iMDC, all output status
LEDs of iMDC-RIM board is lit up. Because network setting information is n
ot enough, iMDC-MAIN recognizes that the communication between iMD
C-MAIN and iMDC-RIM is disconnected. iMDC-RIM operates Power Fail Saf
e mode and all doors are opened.
In this case, after device setting is finished using STARTWATCH ENTERPRIS
E, reboot iMDC-MAIN and iMDC-RIM. Then, iMDC-MAIN recognizes that t
he communication is connected and operated normally.
2. If it occurs during normal operation.
It occurs because network condition between iMDC-MAIN and iMDC-RIM i
s not stable. In this case, check network condition using network manager.
Please refer to description below to test network condition.