background image

IDS 816   700-283-02I    Issued September 2009 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Summary of Contents for 816

Page 1: ......

Page 2: ...IDS 816 700 283 02I Issued September 2009 2...

Page 3: ...Replacing a Faulty Keypad Device 14 4 2 Defaulting Keypads 14 5 Event Log 15 6 Download Code 15 6 1 Programming the Panel 15 6 2 Location Values 15 7 Programming the Panel 16 7 1 Entering Program Mod...

Page 4: ...IDS 816 700 283 02I Issued September 2009 4 14 Programmable Output Options 49 15 Keypad Options 51 16 Installer Options 52 Index of Programming Locations 53 Index 56...

Page 5: ...ion 12 Figure 6 Fire Detect Output Sequence 32 Tables Table 1 Values Represented by Each Zone LED 16 Table 2 Hexadecimal Value 17 Table 3 Location Zone Defaults 19 Table 4 Programmable Zone Types 20 T...

Page 6: ...IDS 816 700 283 02I Issued September 2009 6...

Page 7: ...IDS 816 700 283 02I Issued September 2009 7...

Page 8: ...ndable to sixteen zones via keypad zones zone expander module zone doubling or wireless expansion 2 partitions Optional tamper reporting per zone using double end of line resistors 12K and 4K7 Fully p...

Page 9: ...00 283 02I Issued September 2009 9 2 Installation and Wiring Please refer to Figure 1 Connection Diagram and familiarise yourself with the following sections Figure 1 Connection Diagram without Tamper...

Page 10: ...tors Including Tamper by Zone Zone Doubling All zones must be end of line supervised Any unused zones must be terminated with a 3K3 resistor The end of line resistor must be placed inside or as close...

Page 11: ...double will be violated 3 If the 12K resistor is open circuited the primary zone will indicate a violation i e assuming zone 8 is doubled in this case zone 8 will be indicated as violated 4 If the 4K...

Page 12: ...elephone Ensure the telephone receiver is connected to the communicator terminals marked phone and the incoming line to the terminals marked line 2 6 Programmable Outputs A relay board must be used wh...

Page 13: ...he panel using the reset switch The panel can only be defaulted if a valid installer code is entered and a value of 0 is entered into location 0 4 Enrolling Keypads and Other Devices A new panel suppl...

Page 14: ...fter enrolling a keypad go to location 446 to check the keypad s ID which is a number that corresponds to the order that the keypads were enrolled If the keypad ID is incorrect 2nd keypad has ID 3 for...

Page 15: ...Using the downloading software it is possible to program a location that will either allow or disallow defaulting of the download code This location is only accessible using the download software If...

Page 16: ...LED Value Digit Zone 1 1 Units Zone 2 2 Zone 3 4 Zone 4 4 Zone 5 1 Tens Zone 6 2 Zone 7 4 Zone 8 8 Therefore the displayed value is 15 7 Programming the Panel For all programming procedures the star...

Page 17: ...rogram location you wish to view or change 3 Press the star key The READY indicator will continue flashing and the AWAY indicator will come on 4 The zone LED s will display the data stored in the prog...

Page 18: ...has been finalised press the key to leave the location sub location with the state as indicated by the LED Example Location 40 allows the installer to select up to twelve trouble conditions which may...

Page 19: ...d other Devices page 13 7 6 1 Zone Options LOCATIONS 1 16 Individual Zone Setup Sub location 1 Zone type The first sub locations of program locations 1 16 are used to define the zone characteristics o...

Page 20: ...ic condition This zone type CANNOT be bypassed 4 INSTANT ZONE When the panel is armed the violation of an instant zone will cause the control panel to register an alarm condition 5 ARM DISARM ZONE The...

Page 21: ...an alarm is generated An alarm will also be generated should any single zone remain violated for the entire delay period location 36 An entry exit cannot be cross zoned Swinger Shutdown During a singl...

Page 22: ...winger Shutdown Reporting Code The swinger shutdown zone code will be reported if the system is armed and a zone is automatically bypassed as a result of multiple violations of that zone Sub location...

Page 23: ...mmed zone must remain violated before a violation is registered By default this table is ignored and a Fixed Zone Loop Response of 100ms is used LOCATION 35 Reserved LOCATION 36 Cross zone Delay Timer...

Page 24: ...s keypad beep on communication 6 ON Enables keypad fire medical and panic keys OFF Disables keypad fire medical and panic keys 7 ON Enables the display of bypassed and stay zones when armed in the sta...

Page 25: ...anel will display an instant trouble but will wait for this period of time before REPORTING the mains failure The same time period applies before the restoral event is reported and logged This delay e...

Page 26: ...ouble display OFF Disable box tamper trouble display 9 ON Reserved OFF Reserved 10 ON Enable 485 device trouble display OFF Disable 485 device trouble display 11 ON Enable bus trouble display OFF Disa...

Page 27: ...n audible alarm is registered a delay can be implemented before the siren is triggered The alarm will however be reported as soon as it occurs Enable option 8 location 38 Value Delay 0 3 seconds 1 10...

Page 28: ...this location By default all codes are four digits in length The value programmed into this location has no effect on the download code which is always 4 digits in length Code Old Four digit Code New...

Page 29: ...code is reported when there is a tamper condition on any external device attached to the keypad bus LOCATION 57 Keypad Bus Failure Reporting Code This code is reported when there is a fault on the ke...

Page 30: ...mmable output 2 3 3 Panel programmable output 3 4 4 Panel programmable output 4 5 5 Panel programmable output 5 6 6 Zone expander programmable output 2 7 7 Zone expander programmable output 1 There ar...

Page 31: ...76 Siren trouble programmable output Disabled 77 Aux 12V trouble programmable output Disabled 78 Keypad fuse programmable output Disabled 79 485 device tamper programmable output Disabled 80 485 bus...

Page 32: ...This output follows the hook relay It may be used to trigger switching from the telephone line to a radio transmitter 10 System Clock Options LOCATION 98 System Time Enter the system time The format i...

Page 33: ...t Saving is to commence If the last week of the month is wanted program a five 5 LOCATION 106 Month to Return to Standard Time Enter the month when Daylight Saving reverts to standard time LOCATION 10...

Page 34: ...one violations and restorals will not be reported Violations will however be logged in the event log Panic events will be reported instantly regardless of any selected delay period LOCATION 111 Report...

Page 35: ...ur days 5 Every five days 6 Every six days 7 Every seven days 8 Every eight days 9 Every nine days 10 Every ten days 11 Every eleven days 12 Every twelve days 13 Every thirteen days 14 Every fourteen...

Page 36: ...ogrammed accordingly location 38 the keypad will beep after receiving a handshake from the base station This indicates a successful transmission of data LOCATION 117 Secondary Communicator Format If d...

Page 37: ...m detect 1344 Expansion module fail restore 3333 Long range transmitter fault 1353 AC loss 3321 Loss of supervision RF 1381 AC restoral 3333 RF low battery 1384 Low battery restore 3302 Open by user 1...

Page 38: ...code OFF Disable bypass reporting code 8 ON Enable force reporting code OFF Disable force reporting code 9 ON Enable tamper reporting code OFF Disable tamper reporting code 10 ON Enable tamper restore...

Page 39: ...ON Enable 485 bus tamper reporting code OFF Disable 485 bus tamper reporting code 8 ON Enable box tamper reporting code OFF Disable box tamper reporting code 9 ON Enable dedicated panic reporting cod...

Page 40: ...lf be entered as a 10 All hexadecimal values are entered using the mode key See table 2 page 17 Enter numbers consecutively with no other key presses between each digit To dial a 0 program a table 2 1...

Page 41: ...Download Options LOCATION 123 Download Options LED ON OFF Action 1 ON Enable fax defeat OFF Disable fax defeat 2 ON Enable forced answer OFF Disable forced answer 3 ON Enable auto pickup OFF Disable...

Page 42: ...tition Setup LOCATIONS 128 129 Partition Setup Location 128 Partition One Location 129 Partition Two Sub location 1 Partition Zone Allocation This location is bitmapped with each LED representing a zo...

Page 43: ...en toot on arm OFF Disable siren toot on arm 11 ON Enable siren toot on disarm OFF Disable siren soot on disarm 12 ON Enable the entry beep OFF Disable the entry beep 13 ON Enable the exit beep OFF Di...

Page 44: ...s 3 20 Seconds 11 5 Minutes 4 25 Seconds 12 10 Minutes 5 30 Seconds default 13 15 Minutes 6 45 Seconds 14 18 Minutes 7 1 Minute 15 21 Minutes The exit delay will begin after the entry of a valid user...

Page 45: ...cted in sub location 10 Sub location 10 Auto Arm Days Default all OFF This Bitmapped sub location sets the days on which the partition will auto arm at the time programmed in sub location 9 LED s Days...

Page 46: ...at if one of the above mentioned reporting digits is inadvertently omitted or programmed as a zero the code will not be reported The exception to this rule is when using domestic reporting where only...

Page 47: ...programmable output 1 Pulse high 2 37 Verifies alarm programmable output Disabled 38 Burglary programmable output 2 Pulse high 2 39 Panic programmable output 1 Pulse high 2 40 Fire programmable output...

Page 48: ...29 149 User 14 165 User 30 150 User 15 166 User 31 151 User 16 167 User 32 When the panel is defaulted User Code 1 defaults to 1234 and is a Master User Code All other User Codes are disabled Sub loca...

Page 49: ...is AWAY ARMED Sub location 4 Stay Close Reporting Code This code is reported when the panel is STAY ARMED Sub location 5 Open Reporting Code This code is reported when the panel is disarmed Sub locati...

Page 50: ...hat all days are deselected Sub location 2 Schedule ON Time Enter the time using hhmm format at which the output is to be SET MUST be four digits Sub location 3 Schedule ON Days This bitmapped sub loc...

Page 51: ...ng MODE Partition Number in USER MODE LED ON OFF Action 1 ON The keypad will timeout back to its default partition after it has been used to view another partition OFF The keypad will not timeout and...

Page 52: ...eypad ID 8 Zone 9 16 Installer Options LOCATION 444 Reset Switch Disable Default 0 Value Action 10 Disable reset switch Any other value Enable reset switch For the detailed operation of this switch re...

Page 53: ...40 Trouble Display 26 LOCATION 41 Siren Time Out Period 27 LOCATION 42 Siren Delay 27 LOCATION 43 Keypad Lockout Count Default 4 27 LOCATION 44 Keypad Lockout Time Default 30 seconds 28 LOCATION 45 K...

Page 54: ...ion 2 Primary Account Code 42 Sub location 3 Secondary Account Code 42 Sub location 4 Partition Arm Options 43 Sub location 5 Partition Options 44 Sub location 6 Exit Delay Period 44 Sub location 7 Pr...

Page 55: ...Time 50 Sub location 5 Schedule OFF Days 50 LOCATIONS 400 407 Individual Keypad Setup 51 Sub location 1 Default Keypad Partition Default Partition 1 51 Sub location 2 Keypad Options 51 LOCATION 444 Re...

Page 56: ...er Reporting Code 29 Bypass Reporting Code 22 C Call back Phone Number 42 Clear Programmable Outputs On Disarming 47 Close Reporting Code 49 Communication Delay 34 Communicator Format 36 Communicator...

Page 57: ...y Zone 20 Force Arm Explanation 43 Force Arm Reporting Code 22 Function Driven Programmable Outputs 31 G Global Options 24 Group Reporting Code Enable Disable 38 H Hardware Reset Switch 13 Hexadecimal...

Page 58: ...ons 44 Partition Programmable Outputs 46 Partition Reporting Codes Explanation 46 Partition Setup 42 Partition Zone Allocation 42 Peripheral Devices 10 Phone Line Restoral Reporting Code 29 Primary Ac...

Page 59: ...Entry Exit Zone 20 Silent Zone 21 Siren Cancel Reporting Code 49 Siren Delay 27 Siren Time Out Period 27 Siren Toot on Away Arm Disarm Explanation 43 Siren Trouble Reporting Code 29 Stay Close Report...

Page 60: ...ptember 2009 60 U User Code Properties 48 User Reporting Codes 49 V View Keypad 52 W Warning Zone 20 Wiring 9 Z Zone Doubling 10 Zone Name Editing 22 Zone Properties 21 Zone Reporting Codes 21 Zone Sh...

Page 61: ...IDS816 User Manual 700 283 01H Issued January 2009...

Page 62: ...IDS816 User Manual 700 283 01H Issued January 2009...

Page 63: ...ode Press Tx Button Delete a User Code by Code Master Code 9 User Code Delete a User Code by Slot Number Master Code 10 Slot Number Change Partitions Mode 1 Partition Number Select a Stay Profile Mode...

Page 64: ...IDS816 User Manual 700 283 01H Issued January 2009...

Reviews: