IDS 816 700-283-02I Issued September 2009
10
2.1 Additional Technical Data
A suitable transformer with an output voltage of 16 volts AC ±10% with a 16VA minimum rating
must be used. A 32 VA transformer is recommended for larger installations.
A 12V sealed lead acid battery with a minimum capacity of 7AH must be used. The back up
period after mains failure will depend on the number of keypads, sensors and peripheral devices
connected to the system.
The panel can supply a total continuous current of 750mA to peripheral devices such as keypads,
remotes, receivers, passives etc.
Connect a 12-volt self-driven siren or piezo siren [not a horn speaker] to the siren output.
2.2 End-of-Line Resistors
(Including Tamper by Zone / Zone Doubling)
All zones must be end-of-line supervised.
Any unused zones must be terminated with a 3K3 resistor. The end of line resistor must be
placed inside or as close to the sensor as possible.
If neither zone doubling nor tamper by zone are required the 3K3 resistor must be used.
For zone doubling or tamper per zone, the 4K7 and 12K end-of-line resistors must be connected
as per Figures 2 and 3.
Figure 2 : Tamper by Zone Connection
Tamper operation is as follows:
If the panel is unarmed and a tamper condition occurs, the siren will not sound but a tamper
condition will be reported.
If the panel is armed and a tamper condition occurs an audible alarm will register and a tamper
condition AND zone violation will be reported.
Panic zones always register panic and tamper conditions.
The colour codes for the 12K and 4K7 resistors are as per in Figure 4.
Summary of Contents for 816
Page 1: ......
Page 2: ...IDS 816 700 283 02I Issued September 2009 2...
Page 6: ...IDS 816 700 283 02I Issued September 2009 6...
Page 7: ...IDS 816 700 283 02I Issued September 2009 7...
Page 61: ...IDS816 User Manual 700 283 01H Issued January 2009...
Page 62: ...IDS816 User Manual 700 283 01H Issued January 2009...
Page 64: ...IDS816 User Manual 700 283 01H Issued January 2009...