38
IDS 805 Installer Manual 700-266-02H Issued September 2009
LOCATION 169
Siren Tamper Programmable Output (Default = 0)
The siren tamper output will be triggered if the siren wire is open circuit for more than 5 seconds or the
fuse has blown.
LOCATION 170
Box Tamper Programmable Output (Default = 0)
The box tamper output will be triggered if the panel box is opened.
Set System Time, Auto Test Time, Automatic Arm Time
All time values must be entered as a 4-digit value in hours and minutes in a 24-hour format i.e. 1.00pm is
entered as 1300.
To view and change values in these locations:
1.
Enter programming mode by entering a valid
[INSTALLER CODE]
followed by
[*]
.
2.
Enter
[LOCATION NUMBER]
e.g. 800 followed by
[*].
3.
The value displayed by the LED's will be the hour value.
4.
Press
[*]
and the LED’s will display the minutes value.
It is necessary to display the hours and minutes separately as it is not possible to display 4 digits on the
keypad simultaneously.
LOCATION 800
System Time (Default = 0000)
This location is used for setting the system clock time.
LOCATION 801
Auto Test Time (Default = 0100)
This location is used for setting the time of day at which the auto test will be reported.
EXAMPLE:
If a value of 6 was programmed into location 147 and 1400 was programmed into location 801, the auto
test would be sent every seven days at 2:00pm.
LOCATION 802
Auto Arm Time (Default = 9999)
This location sets the time at which the panel will automatically arm every day (if enabled). The auto arm
feature is disabled by entering an invalid time greater than 2400 e.g. 9999.
Summary of Contents for 805
Page 1: ...1 IDS 805 Installer Manual 700 266 02H Issued September 2009...
Page 2: ...2 IDS 805 Installer Manual 700 266 02H Issued September 2009...
Page 5: ...5 IDS 805 Installer Manual 700 266 02H Issued September 2009...
Page 6: ...6 IDS 805 Installer Manual 700 266 02H Issued September 2009...
Page 48: ...48 IDS 805 Installer Manual 700 266 02H Issued September 2009...