Installation instructions AERO ILM
25
m
in. 800
mm
Installation
- The heat pump has to be installed in
a frost-proof room! (room temperature
PXVWOLHEHWZHHQ&DQG&
- In order to minimize oscillations and sounds
within buildings, heat pumps should be decou-
pled as far as possible from the building mass.
It is principally recommended to avoid installing
KHDWSXPSVRQFHLOLQJVDQGÀRRUVLQOLJKWZHLJKW
FRQVWUXFWLRQ,QWKHFDVHRIÀRDWLQJÀRRUVFUHHG
ÀRRUVFUHHGDQGLPSDFWVRXQGLQVXODWLRQVKRXOG
be omitted around the heat pump.
- The installation in wet or damp environments or
in areas exposed to dust or explosion hazards is
non-permissible.
- If refrigerant escapes from the installation site,
this must not enter adjacent rooms, stairways,
yards, corridors or drainage systems and a
hazard-free drainage must be ensured.
- In the case of danger, leave the installation site
immediately.
- If the size of the installation site falls below the
requested minimum size, this has to be designed
as machinery room in compliance with EN 378.
-
,I WKH HPHUJHQF\ YHQWLODWLRQ LV QRW VXႈFLHQW
mechanical ventilation must be provided. A
mechanical ventilation shall be installed with
an independent emergency control beyond the
installation site and near the door to that area.
- Heat pumps must not be installed in rooms with
KLJK(0&ORDG
- Air intakes and outlets have to be safeguarded
against theft by appropriate on-site measures.
5.7. Installation location
Opposite the outlet opening in the heat
pump the pre-installed condensate
KRVH PXVW EH SRVLWLRQHG WR GUDLQ Rႇ
condensate. For this purpose a drain-
age must be provided.
Heating connections /
&RQGHQVDWLRQUXQRႇ
Electrical connections
5.8. Space requirements and accessibility
In order to guarantee maintenance and operation of
the heat pump, a minimum distance of 800 mm has
to be observed on the front side (for operation and
maintenance).
By observing this distance an unobstructed system
maintenance and operation can be guaranteed.