T
H E
P O W E R
F A M I L Y
(C) IDM ENERGIESYSTEME GMBH
2. Allgemeine Informationen
Installation TERRA S/W
8
1
2
3
4
5
6
7
8
9
10
11
12
13
1
2
Description
De
scription
Technical Data TERRA S/W with R407C
Type TERRA (BA) (HGL)
Unit
5 S/W
7 S/W
8 S/W
10 S/W
12 S/W
Dimensions (H x W x D)
cm
116/62/76
116/62/76
116/62/76
116/62/76
116/62/76
Weight HGL/Basic
kg
130/116
136/122
144/130
150/136
156/140
Electrical connection of the primary circuit
V/Hz
3x400 / 50
3x400 / 50
3x400 / 50
3x400 / 50
3x400 / 50
Power consumption compressor
A
4.2
5.1
6.3
7
10
Start-up current compressor (with soft start)
A
10.5
12.75
15.75
17.5
25
Electrical connection control circuit
V/Hz
230 / 50
230 / 50
230 / 50
230 / 50
230 / 50
Fuse control circuit
A
13
13
13
13
13
Refrigerant
R 407 C
R 407 C
R 407 C
R 407 C
R 407 C
Filling volume
kg
1.8
2.05
2.2
2.5
2.6
Filling volume compressor oil
l
1
1
1.1
1.1
1.36
Minimum size installation room
m³
5.8
6.1
6.5
6.8
8.4
Minimum size ventilation opening (natural)
m²
0.19
0.19
0.20
0.20
0.23
Minimum air fl ow (mechanical)
m³/h
75
77
80
83
95
2.6. Technical data
For the dimensioning of the fuse to be connected in series in the primary circuit, the nominal
current of the compressor and the on-site heat source pump as well as, if available, of the inter-
mediate circuit pump must be added.
Recommended power protection switch types: 3-pole Type C, K