IDEC SmartRelay installation and wiring
IDEC SmartRelay Manual
25
Sensor connections
Connecting glow lamps and 2-wire proximity switches (Bero)
to FL1C-H12RCC/FL1C-B12RCC or FL1B-M08C2R2 (AC)
Take the quiescent current of any 2-wire proximity switches
used into account. The level of the quiescent current of some
2-wire proximity switches is high enough to trigger a logical
"1" signal at the IDEC SmartRelay input. You should there-
fore compare the quiescent current of the proximity switches
with the technical data of inputs Appendix A.
L1
N
N
L1
C