FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
C
OMMUNICATION
M
ANUAL
FC9Y-B1730
4-15
4: M
AINTENANCE
C
OMMUNICATION
4.
Click
Connection Settings
.
5.
Click
Communication Mode
for the port to be used and select communication mode of the connection to use.
6.
Set the parameters to match the communication format used by the computer or operator interface.
Note:
The number of clients that can be connected to the FC6A Series MicroSmart simultaneously is one client per connection. If connections 1 to
8 are all set to the maintenance communication server, eight clients can connect to the FC6A Series MicroSmart at the same time.
7.
Click
OK
.
This completes maintenance communications settings.
Local Host Port No.
: 2101 (The port number that the FC6A Series MicroSmart uses for the maintenance
communication server)
Receive Timeout (ms)
: 2000 (100 to 25500)
Allow Access by IP Address : Disabled (Enabling this option makes it possible to prevent access from devices having any IP
addresses other than the one entered.)