5: U
SER
C
OMMUNICATION
I
NSTRUCTIONS
5-30
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
C
OMMUNICATION
M
ANUAL
FC9Y-B1730
4.
Since the
RXD (Receive)
dialog box reappears, repeat the above procedure. In the
Data Type Selection
dialog box, click
Skip
and click
OK
. Next, in the
Skip
dialog box, type
02
in the
Digits
box and click
OK
.
5.
Again in the
Data Type Selection
dialog box, click
Constant (Character)
and click
OK
. Next, in the
Constant
(Character)
dialog box, type
,
(2Ch)
in the
Character
box to program a comma as a constant to verify. When finished, click
OK
.
6.
Again in the
Data Type Selection
dialog box, click
Variable (DR)
and click
OK
. Next, in the
Variable (Data Register)
dialog box, type
D10
in the
DR No.
box and click
ASCII to Binary
to select ASCII to binary conversion. Enter
4
in the
Digits
box (4 digits) and
2
in the
REP
box (2 repeat cycles). Click
Variable
, select
HEX
, and type
0D
to designate a delimiter. When
finished, click
OK
.
7.
Again in the
Data Type Selection
dialog box, click
BCC
and click
OK
. Next, in the
BCC
dialog box, enter
01
in the
Calculation Start Position
box, select
ADD
for the
Calculation Type
, click
Binary to ASCII
for the
Conversion Type
,
and click
2
for the
Digits
. When finished, click
OK
.
Delimiter