FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
C
OMMUNICATION
M
ANUAL
FC9Y-B1730
2-11
2: D
EVICE
D8124
Cartridge Slot 2 Information
Type ID/Status
―
R
D8125
System Software Version
―
R
D8126
Cartridge Slot 3 Information
Type ID/Status
―
R
D8127
System Software Version
―
R
D8128 to
D8169
— Reserved —
―
―
D8170
Analog Cartridge I/O AI2/AQ2
Every scan
R
D8171
Analog Cartridge I/O AI3/AQ3
Every scan
R
D8172
Analog Cartridge Status AI2/AQ2
Every scan
R
D8173
Analog Cartridge Status AI3/AQ3
Every scan
R
D8174
Analog Cartridge I/O AI4/AQ4
Every scan
R
D8175
Analog Cartridge I/O AI5/AQ5
Every scan
R
D8176
Analog Cartridge Status AI4/AQ4
Every scan
R
D8177
Analog Cartridge Status AI5/AQ5
Every scan
R
D8178
Analog Cartridge I/O AI6/AQ6
Every scan
R
D8179
Analog Cartridge I/O AI7/AQ7
Every scan
R
D8180
Analog Cartridge Status AI6/AQ6
Every scan
R
D8181
Analog Cartridge Status AI7/AQ7
Every scan
R
D8182 to
D8191
— Reserved —
―
―
D8192
High-speed
Counter
(Group 2/I1)
High Word
Current Value/Frequency Measurement (I1) Current
Value
Every scan
R
D8193
Low Word
Every scan
R
D8194
High Word
Preset Value
―
R/W
D8195
Low Word
―
R/W
D8196
High Word
Preset Value
―
R/W
D8197
Low Word
―
R/W
D8198
High-speed
Counter
(Group 6/I7)
High Word
Current Value/Frequency Measurement (I7) Current
Value
Every scan
R
D8199
Low Word
Every scan
R
D8200
High Word
Preset Value
―
R/W
D8201
Low Word
―
R/W
D8202
High Word
Preset Value
―
R/W
D8203
Low Word
―
R/W
D8204 to
D8209
— Reserved —
―
―
D8210
High-speed
Counter
(Group 1/I0)
High Word
Current Value/Frequency Measurement (I0) Current
Value
Every scan
R
D8211
Low Word
Every scan
R
D8212
High Word
Preset Value
―
R/W
D8213
Low Word
―
R/W
D8214
Interrupt Input Jump Destination Label No. (I7)
―
R/W
D8215
Interrupt Input Jump Destination Label No. (I0)
―
R/W
D8216
High-speed
Counter
(Group 1/I0)
High Word
Preset Value
―
R/W
D8217
Low Word
―
R/W
D8218
High-speed
Counter
(Group 3/I3)
High Word
Current Value/Frequency Measurement (I3) Current
Value
Every scan
R
D8219
Low Word
Every scan
R
D8220
High Word
Preset Value
―
R/W
D8221
Low Word
―
R/W
D8222
High-speed
Counter
(Group 4/I4)
High Word
Current Value/Frequency Measurement (I4) Current
Value
Every scan
R
D8223
Low Word
Every scan
R
D8224
High Word
Preset Value
―
R/W
D8225
Low Word
―
R/W
D8226
High-speed
Counter
(Group 5/I6)
High Word
Current Value/Frequency Measurement (I6) Current
Value
Every scan
R
D8227
Low Word
Every scan
R
D8228
High Word
Preset Value
―
R/W
D8229
Low Word
―
R/W
Device
Address
Description
Update Timing
R/W