Optional Settings: SMTP Authentication
Depending on the SMTP server, SMTP-AUTH or SMTPs authentication may be required to send e-mails.
The FC6A Series MicroSmart supports SMTP-AUTH and SMTPs authentication, so if the SMTP server requires authentication, it can
send e-mails using this function.
Contact the administrator of the SMTP server to confirm if it requires authentication.
(6) Authentication is required to send e-mail
Check if the sending e-mail server requires the SMTP authentication with the login method.
(7) Account Name
Specify the account name used for the login authentication. A maximum of 40 ASCII characters can be entered.
(8) Password
Specify the password used for the login authentication. A maximum of 40 ASCII characters can be entered.
(9) Use data registers to configure E-mail settings
When the check box for this option is selected, the basic settings and authentication settings can be configured using strings and
numeric values stored in data registers. E-mails are sent using the settings stored in 107 words of data registers starting from
the specified data register.
For each setting item, the start address and end address as well as details about the setting value are as follows.
*1 The string set to "Number of used words - 1" words is valid as the setting value. In order to represent the end of the string, the final word is
handled as if 0000h was stored in it, regardless of the actual values in the data registers.
*2 If the set string is shorter than "Number of used words - 1", fill the data after the string with 00h.
Setting Item
Data Type
Number
of Used
Words
Start Address
of Setting
Item
End Address of
Setting Item
Setting Value
SMTP Server
String
(40 characters)
Starting data
register
Starting data
r20
Specify the IP address or the host name of the
sending e-mail server that is used to send e-
mails as a string.
SMTP Server Port
Decimal value
1
Starting data r21
Specify the port number of the sending e-mail
server that is used to send e-mails as a decimal
value.
Sender E-mail
Address
String
(40 characters)
Starting data
r22
Starting data
r42
Specify the e-mail address that is included in the
sender field of the e-mails to be sent from the
FC6A Series MicroSmart as a string.
Sender Name
String
(40 characters)
Starting data
r43
Starting data
r63
Specify the name that is included in the sender
field of the e-mails to be sent from the FC6A
Series MicroSmart as a string.
Authentication is
required to send
Decimal value
1
Starting data r64
When authentication is required by the sending
e-mail server that is used, specify 1. When
authentication is not required, specify 0.
Account Name
String
Starting data
r65
Starting data
r85
Specify the account name that is used with
authentication as a string.
Password
String
21
Starting data
r86
Starting data
r106
Specify the password that is used with
authentication as a string.
Use secure
connection (SSL)
Decimal value
1
Starting data r107
When SSL communication is required with the
sending e-mail server that is used, specify 1.
When this communication is not required,