System Manual HS3A-H21M4
24
Technical data
Note!
If a product data sheet is included with the product, the information on the data
sheet applies in case of discrepancies with the operating instructions.
Technical data for HS3A
Parameter
Value
Unit
min.
typ.
max.
Housing material
PBT
Weight
0.4
kg
Ambient temperature
at U
B
= 24V DC
-20
-
+55
℃
Storage temperature
-25
-
+70
Degree of protection
P67
Safety class
III
Degree of contamination
3
Installation position
Any
Connection type
M12 plug connector,8-pin
Operating voltage U
B
(reverse polarity pro-
tected, regulated, residual ripple < 5%)
24±15% (PELV)
V DC
For the approval according to UL, c-UL
the following applies
Operation only with UL Class 2 power supply, or equivalent measures
Current consumption
80
mA
Switching load according to UL, c-UL
24V DC, class 2
External fuse (operating voltage)
0.25
-
8
A
Safety outputs OA/OB
Semiconductor outputs, p-switching, short circuit-proof
-Output voltage U(OA)/U(OB)
1)
HIGH U(OA)
U
B
-1.5
-
U
B
V DC
HIGH U(OB)
LOW U(OA)/U(OB)
0
-
1
Switching current per safety output
1
-
400
mA
Utilization category
acc. to EN IEC 60947-5-2
DC-13 24 V 400mA
Caution: outputs must be protected with a free-wheeling diode in case of
inductive loads.
Off-state current I
r
≤
0.25
mA
Monitoring output OUT
1)
p-switching, short circuit-proof
-Output voltage
0 8×U
B
U
B
V DC
-Max load
-
200
mA
Rated insulation voltage U
i
-
-
300
2)
V
Rated impulse withstand voltage U
imp
-
-
1 5
kV
Conditional short-circuit current
100
A
Resilience to vibration
In acc. with EN IEC 60947-5-2
Switching frequency
-
-
1
Hz
Repeat accuracy
≤
10
%
EMC protection requirements
In acc. with EN IEC 60947-5-3 and EN IEC61326-3-1
Ready delay
-
8
-
s
Risk time for single device
-
-
260
ms
Delay of the risk time per device
5
ms
Switch-on time of safety outputs
-
-
400
ms
Simultaneity monitoring, safety inputs
-
-
150
ms
Discrepancy time
-
-
10
ms
Test-pulse duration at the safety outputs
1
ms
Reliability values according to EN ISO 13849-1
Category
4
Performance Level
PL e
PFH
D
2.1 X 10
-9
/h
3)
Mission time
20
years
1) Values at a switching current of 50mA without taking into account the cable lengths.
2) Tested by employers' liability insurance association up to 75V.
Table 5