Diagnostics
HR9Z-B2190 8/2020
77
Diagnostics via Status Output Z1
Overview
The pulsed output Z1 provides diagnostics information in the form of a bit pattern.
Refer to the chapter Electrical Installation
) for additional information on wiring the Z1.
Diagnostics Codes
The device encodes diagnostics information into sequences of 10 bits with a total of 2 s (each bit
200 ms).
The first four bits (0010) represent the beginning of a bit sequence. The next six bits contain the
diagnostics code itself.
The following table lists the bit sequences of the diagnostics codes, the description of the
corresponding status as well as correctives, if applicable.
WARNING
INCORRECT USE OF OUTPUT
Do not use the additional output Z1 for safety-related purposes.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Bit sequence
Description
Correctives
Type
(1)
0010101101
Supply voltage out of
tolerance.
Verify correct wiring.
Use a suitable power supply.
E
0010000011
General error detected.
Verify correct wiring.
Perform a power cycle.
If the error persists, replace the device.
E
0010000111
Configuration error
detected. The position of
at least one of the
selectors has been
modified during
operation.
Verify that the position of the selectors is appropriate for
the application to be implemented.
Perform a power cycle.
If the error persists, replace the device.
E
(1) Type of message: E = Error detected, A = Alert, S = Status information
Summary of Contents for HR6S Series
Page 1: ...http www idec com HR6S AB Safety Module Original instructions HR9Z B2190...
Page 8: ...8 HR9Z B2190 8 2020...
Page 14: ...14 HR9Z B2190 8 2020...
Page 20: ...Introduction 20 HR9Z B2190 8 2020...
Page 54: ...Installation 54 HR9Z B2190 8 2020...
Page 80: ...Diagnostics 80 HR9Z B2190 8 2020...
Page 86: ...Accessories Service Maintenance and Disposal 86 HR9Z B2190 8 2020...