background image

10 / 18

• Manual or automatic start
• 3 Enabling paths, 1 signalling path
• Feedback loop to monitoring external contactors

Application

Safety  systems  are  comprised  of  many  components.    No  one  safety

component  will  insure  the  safety  of  the  system.    The  design  of  the

complete safety system should be considered before you begin.  It is very

important to follow applicable safety standards when installing and wiring

these components.

Disclaimer

Electrical  equipment  should  be  installed,  operated,  serviced,  and

maintained only by qualified personnel.

Function

The supply voltage has to be connected to terminals A1/A2 according to

the  voltage  printed  on  the  product  label.  The  control  units  must  be

connected as follows:
Use of one input channel:
Connect  the  control  units  (emergency  stop)  contacts  to  terminals  S11-

S12. Terminals S21-S22 and B1-S12 must be jumpered.
Use of two input channels:
Connect the control units (emergency stop) contacts to terminals S11-S12

and S21-S22 . Terminals B1-S11 must be jumpered.
Using the two channel connection, the two input circuits are supplied with

different polarities, which enables the detection of short circuits between

the + and the -. If the different polarity is not desired, connect the control

units to terminals S11-S12 and S11-B1, and terminals S21-S22 must be

jumpered. In this operation mode a detection of short circuits between the

+ and the - is not possible (pinched cables will not be detected).
The  start  button  as  well  as  the  N/C  contacts  of  the  external  relays  or

contactors switched by the safety function outputs have to be integrated

in the feedback loop between the terminals S33 and Y2. The device can

only be switched on if the relevant relays are de-energized after a

preceding stop command. The feedback loop must be closed for every

new start command. If necessary, terminal Y1 can be used as additional

terminal for ease of wiring. Terminal Y1 is not connected internally.
The function of the start button is determined by the location of a jumper. If

terminals  Y3-Y5  are  interconnected,  the  start  button  is  integrated  in  the

monitoring. In this configuration, the outputs of the module are  activated at

the  trailing  edge  of  the  start  signal  (at  the  release  of  the  start  button).  If

terminals Y3-Y4 are jumpered, the outputs are activated immediately after

actuation of the start button provided that the input device circuits are closed.
The  configuration  jumper  between  terminals  Y3-Y5  or  Y3-Y4  must  be

short and connected directly to the device.

It is imperative to use only one of the two possible jumpers  (i.e., either Y3-

Y5 or Y3-Y4). Do not make any other connections to these terminals or

The HR1S-ATE module is equipped with an internal electronic fuse, which

protects the module against damage by external short circuits (e. g. short

circuits between the + and the - of the input circuits). A few seconds after

elimination of the abnormal condition, the module is operative again.

Proper use

The  device  is  for  monitoring  sensors  (e.g.  emergency  stop  buttons,

position  switches)  that  are  used  as  part  of  the  safety  equipment  of

machines for the purpose of protecting people, material and machinery.

Note

• The entire system/machine must undergo validation in accordance 

with the applicable standards on the basis of this.

• The module contains electro-mechanical relays. Therefore his 

indicated performance level and his MTTF

d

 value depend on the load 

and on the operating cycles in the application. The above mentioned 

performance level and MTTF

d

 values are suitable for nominal load and 

maximum 6.336 switching cycles per year or for low load and 

maximum 316.800 switching cycles per year.

• If the current load is known, use the diagram for the electrical service 

life (see page 16/18) to calculate the maximum number of switching 

cycles. 

The specified performance level can only be assured for 

the number of switching cycles calculated using this method.

The device must be replaced on reaching this maximum figure.

Thereby the lifetime of the device must not be exceeded.

• Operating the device not within the specifications may lead to 

malfunctions or the destruction of the device.

• The supply input A1 serves as a control input. This may lead to short 

disruptions or a lowering below the operating voltage U

B

 in order to 

switch to the release path.

• Expansion devices or external contactors with positively driven 

contacts can be used to duplicate the enabling current paths.

• The emergency stop chain must be closed before the reset button is 

activated.

• If magnetic switches with reed contacts or sensors with semiconductor 

outputs are connected the switch ON peak current must be noticed 

(see Technical Data).

• Please consult the installation notes.

Note

Please observe instructions from safety authorities.

Note

There are no user serviceable components in the module.  Use only the

hard contacts outputs between terminals 13-14 and 23-24 for stop category

0, and between terminals 57-58, 67-68 and 77-78 for stop category 1.

 

CAUTION

EQUIPMENT DAMAGE
• Install external fuse as shown on the "WIRING DIAGRAM FOR 

MODULE HR1S-ATE SAFETY RELAY."

• See also the "TECHNICAL DATA" of this Instruction Sheet for 

information on output protection.

Failure to follow this instruction can result in injury or equipment 

damage.

!

!

!

!

!

HR1S-ATE SAFETY  RELAY MODULE OPERATING INSTRUCTIONS

The HR1S-ATE module provides an interruption of one or several circuits and 

is designed to be integrated into emergency stop or safety circuits conforming 

to  EN/IEC  60204-1.  It  meets  the  requirements  of  European  standard  EN 

ISO/ISO  13850  for  emergency  stop  equipment  and  EN/IEC  60204-1  for 

safety  circuits  in  general.  These  standards  are  related  in  particular  to  

applications in which a single emergency stop command must open several 

circuits  (emergencystop  by  indirect  action).  The  module  meets  also  the 

safety requirements for electrical monitoring of limit switches at interlocking 

guards (EN 1088).
In  addition  to  the  two  direct  opening  safety  function  outputs  of  stop 

category  0  (EN  ISO/ISO  13850,  EN/IEC  60204-1),  the  module  is 

equipped with three additional delayed opening outputs of stop category 

1. These additional outputs allow a controlled slowing-down of the drive 

units  to  obtain  the  definitive  stop  (e.  g.  motor  braking  by  means  of  a 

variable speed drive). At the end of the preselected delay time the power 

supply is disconnected by opening the delayed output circuits. The time 

delay of the three output circuits between the terminals 57-58, 67-68 and 

77-78 can be adjusted from 0 to 30 seconds by means of a 12 position 

selector switch located in the front cover. Use a screwdriver to set the 

desired time delay.

The module is designed for use with one or two input channels. Due to  

the  extended  possibilities  of  fault  detection  we  recommend  the  use  of    

two  input  channels.  In  this  operation  mode  the  connection  cables  are 

integrated in the monitoring and all first faults will be detected. 

• The  performance  level  and  safety  category  in  accordance  with  EN 

ISO/ISO 13849-1 depends on the external wiring, the application case, 

the choice of control station and how this is physically arranged on the 

machine.

• The  user  must  carry  out  a  risk  assessment  in  accordance  with  EN 

ISO/ISO 14121-1.

No responsibility is assumed by IDEC for any consequences arising out 

of the use of this material.

the device may become inoperative.

Summary of Contents for HR1S-ATE

Page 1: ...1 68 78 Y88 Y89 Y90 58 Y91 67 77 57 Y 24 23 14 13 20 2 4 6 8 10 15 25 30 0 0 5 1 Time s A1 A2 Fuse Input A S12 Input B S22 Stop 1 68 78 Y88 Y89 Y90 58 Y91 67 77 57 Y 24 23 14 13 20 2 4 6 8 10 15 25 30...

Page 2: ...42 IDEC HR1S ATE EN IEC60204 1 EN ISO ISO 13850 EN IEC 60204 1 EN 1088 0 EN ISO ISO 13850 EN IEC 60204 1 2 1 3 57 58 67 68 77 78 3 12 0 30 2 2 EN ISO ISO 13849 1 EN ISO ISO 14121 1 PL MTTFd PL MTTFd 6...

Page 3: ...78 Y88 Y89 Y90 Y91 Y A1 A2 S12 S22 Stop1 4A 0 1 PLC S1 2 NC S2 ESC Y1 S33 Y2 S3 S11 S21 A1 13 77 S22 B1 S12 23 57 67 S2 S1 HR1S ATE S11 S21 A1 13 77 S22 B1 S12 23 57 67 S1 HR1S ATE 1 NC A2 S33 Y1 Y2 Y...

Page 4: ...L2 U T1 V T2 W T3 L1 R1 T1 FW RV HR1S ATE 0 30 s F2 PLC 1 2 A1 A2 Y88 Y89 Y90 Y91 Y S12 S22 Stop1 1 2 PLC 1 A1 A2 Fuse 2 Input A S12 3 Input B S22 4 Stop 1 LED LED1 A1 A2 Fuse A1 A2 LED2 Input A S12...

Page 5: ...Y5 Y3 Y4 NC1 NC2 tmax 75 ms Tv 0 30 77 78 NO 23 24 NO Y88 A1 A2 67 68 NO 57 58 NO 13 14 NO Y90 S22 Y91 Stop 1 Y89 S12 Y3 Y4 S33 Y1 Y90 S22 Y89 S12 NC2 NC1 NC1 NC2 HR1S ATE SAFETY RELAY MODULE OPERATI...

Page 6: ...Nm 4 4 lb in 2 m m 1 2 0 2 24 18 AWG1 m m 5 1 2 0 2 24 16 AWG1 7 mm 0 28 in 0 25 1 mm 2 22 18 AWG1 0 5 1 5 mm 2 20 16 AWG1 0 5 Nm 4 4 lb in 1 AWG EN IEC 60947 1 1 5 1 7 0 6 C E I N E N I D m m 5 3 EN...

Page 7: ...n 45 mm 1 77 in 35 mm 1 38 in HR1S ATE5110 99 mm 3 89 in 114 mm 4 48 in 45 mm 1 77 in 35 mm 1 38 in HR1S ATE5110P HR1S ATE5110P HR1S ATE5110 HR1S ATE5110P E5110P T A S 1 R H E5110 T A S 1 R H Vue de f...

Page 8: ...installation des appareils respectez les r glementations de s curit pour usage lectrique et de la caisse de pr voyance contre les accidents L ouverture du bo tier ou toute autre manipulation entra ne...

Page 9: ...i ne sont pas ou insuffisament integr dans le circuit de s curite b l utilisateur ne respecte pas les exigences des normes de s curit pour le service le r glage et la maintenance de la machine Il est...

Page 10: ...or for low load and maximum 316 800 switching cycles per year If the current load is known use the diagram for the electrical service life see page 16 18 to calculate the maximum number of switching...

Page 11: ...ht galvanisch getrennten Ger ten auf dem Steuerkreis Netzpotential anliegen Beachten Sie f r die Installation der Ger te die Sicherheitsvorschriften der Elektrotechnik und der Berufsgenossenschaft Dur...

Page 12: ...ktronische Sicherung sch tzt das Ger t vor Zerst rung durch u ere Kurzschl sse z B bei Querschl ssen in der Eingangsbeschaltung Nach Beseitigung der Fehlerursache ist der Baustein nach einigen Sekunde...

Page 13: ...Y2 Boucle de retour Feedback loop R ckf hrkreis S3 S11 S21 A1 13 77 S22 B1 S12 23 57 67 S2 S1 HR1S ATE Raccordement de plusieurs boutons d ARRET D URGENCE Connection of several EMERGENCY STOP buttons...

Page 14: ...2 indique l tat du premier circuit d entr e entre les bornes S11 S12 Lorsque le potentiel positif est pr sent sur la borne S12 la DEL 2 s allume DEL 3 Input B S22 La DEL 3 indique l tat du deuxi me c...

Page 15: ...ton Starttaste Sortie 77 78 F Output 77 78 NO Ausgang 77 78 S Sortie 23 24 F Output 23 24 NO Ausgang 23 24 S Sortie statique Y88 A1 A2 Transistor output Y88 A1 A2 Transistorausgang Y88 A1 A2 Sortie 67...

Page 16: ...20 AWG1 stranded 0 14 0 75 mm2 26 20 AWG1 Stripping length 7 mm 0 28 in Flexible with cable end withoutplasticsleeve 0 25 1 mm2 24 18 AWG1 Flexible with TWIN cable end with plastic sleeve 0 5 1 5 mm2...

Page 17: ...insulation voltage 300 V EN IEC 60664 1 Supply voltage UE according to IEC 60038 24V 50 60 Hz 10 20 24V 20 20 Refer to device nameplate for supply voltage Max protection 4 A fuse gG Power consumption...

Page 18: ...CE DE LA DECLARATION NOM ADRESSE 0044 44 205 10 380862 0014 T V NORD CERT GMBH Langemarckstr 20 D 45141 Essen DATED REFERENCE DIRECTIVE EN 60204 01 2006 DIN EN 60204 01 2007 06 DIRECTIVE 2006 95 EC OF...

Reviews: