Technical data
306
IDEC SmartRelay Manual
(1): When FL1E-H12SND or FL1B-M08B1S2 are switched on, signal 1 is sent to the
digital outputs for about 50 microseconds. Take this into account, especially when
using devices that react to short pulses.
(2) The maximum switching rate is only dependent on the switching program’s cycle
time.
Line length (shielded and twisted)
10 m
Error limit
+/- 1.5% at full scale
Digital outputs
Number
4
Output type
Transistor, current-sourcing
(1)
Electrical isolation
No
In groups of
Control of a digital input
Yes
Output voltage
Supply voltage
Output current
max. 0.3 A
Short circuit-proof and overload-proof
Yes
Short circuit current limitation
Approx. 1 A
Derating
none; across the entire temperature range
Short circuit-proof cos 1
not applicable for this module
Short circuit-proof cos 0.5 to 0.7
not applicable for this module
Parallel output circuit for power increase
Not permitted
Protection of output relay (if desired)
Switching rate
(2)
Mechanical
not applicable for this module
Electrical
10 Hz
Ohmic load/lamp load
10 Hz
Inductive load
0.5 Hz
FL1E-H12SND
=
<