IDEC SmartRelay functions
152
IDEC SmartRelay Manual
Parameter assignment screen form
View of the parameter assignment screen form, for example
for Cam1 and the Pulse setting:
B1 1+
D=MTWTFSS
On =06:30
Off=08:00
B1 4+
Pulse=Off
Block B1
Cam 1
See Showing/hiding parameters -
Parameter protection mode on
page 90
Weekdays (daily)
On-time (06.30 h)
Off-time (08:00 h)
Pulse form
Pulse setting: On or Off
Days of the week
The suffix of ”D=” (Day) has the following meaning:
•
M : Monday
•
T : Tuesday
•
W : Wednesday
•
T : Thursday
•
F : Friday
•
S : Saturday
•
S : Sunday
Uppercase letters indicate a specific day of the week. A “-”
indicates no selection for the day of the week.
On-/Off-times
Any time between 00:00 h and 23:59 h is possible.You can
also configure the on time to be a pulse signal. The timer
block will be activated at the specified time for one cycle and
then the output is reset.
- -:- - means: No on-/off-times set.