background image

8

Super Plus  -  

Installation and Servicing

6.

  Flue products must not be allowed to enter the       

 

boilerhouse or adjacent buildings.

7.

  Refer also BS.6644 and to IGE/UP/10 Installation of Gas 

Appliances in Industrial and Commercial Premises and IM/22 

for further guidance.

AIR SUPPLY

Detailed recommendations for air supply are given in BS.6644 

which MUST be consulted before proceeding.

Contamination of the air supply from any external source must be 

avoided - with particular reference to dust, insulation debris, and 

flue products and concrete floors must be sealed. If any work is to 

be carried out in the boilerhouse which is likely to generate dust 

(e.g. structural alterations or lagging pipework), it is recommended 

that the boiler be shut down and the modules covered with a dust 

sheet, otherwise the boiler may require cleaning and servicing.

1. 

In particular the contamination of the air supply with chlorides 

must be avoided as they will cause the deterioration of the 

aluminium heat exchanger.

2.

  The boiler requires ventilation openings at BOTH high and low 

levels, direct from outside, and allowance MUST be made for 

stabiliser dilution in all cases.

3.

  Mechanically forced ventilation systems must include provision 

for boiler shut down in the event of fan failure.

4

.  High speed air streams within the boilerhouse must be 

avoided.

5.

  Extraction mounted ventilation fans alone are NOT permitted.

6.

  The minimum effective areas of the permanent air vents direct 

from the outside by natural ventilation are as follows:

 

Required area (cm

2

) per kW of total rated input (net)

 

  Boiler room 

Enclosure

 

Low level (inlet) 

10

 

High level (outlet) 

5

 

Note: Where a boiler installation is to operate in summer 

months (e.g. DHW) additional ventilation requirements 

are stated, if operating for more than 50% of time (refer to 

BS6644).

7.

  The minimum air requirements by mechanical ventilation    

are as follows:

 

Table 2

 

Mechanical ventilation flow rates

 

Type of boiler           

Flow rate per KW total rated heat input (net)

 

 

Inlet air 

Extract

  

(Combustion 

air

   

ventilation) (ventilation)

  Forced/induced 

2.6 m

3

/h 1.25m

3

/h

  draught boilers 

 

± 0.18m

3

/h

 

A purpose designed flueing ventilation system based solely on a 

high level permanent opening to an otherwise sealed boiler-house 

or compartment may be used, provided that specialist advice is 

taken and that the combustion air and ventilation requirements of 

the boiler is provided in line with BS.6644. In addition this boiler 
house temperature must be prevented from exceeding 32

 o

C at 

mid-level.  BS 6644 provides details of temperature requirements.

LOCATION

The floor must be flat, level and capable of supporting the weight 

of  the  WET  boiler  pipework.  In  addition,  concrete  floors  must 

be sealed. The siting of the boiler must be in accordance with 

the guidance given in BS.6644 and with reference to minimum 

boilerhouse clearances - refer to Fig. 5.

Inflammable materials MUST NOT be placed in close proximity to 

the appliance. Materials giving off flammable vapours MUST NOT 

be stored in the same room as the appliance.

Fig.5  Recommended Boiler House Clearances

 for Comfortable Servicing Access (Plan View)

Note:

 

Headroom must be the boiler height 

(Table 1) Plus any pipework and flue 

requirements

CONNECTION TO GAS SUPPLY

The gas installation MUST be in accordance with the requirements 

of the local gas region (refer also to CP 331:3 and CP 332:3 where 

applicable).

The gas supply must be capable of maintaining a minimum pressure 

as indicated in Table 1, measured at the inlet to the boiler, with all 

modules firing (gas consumption is given in

Table 1.)  Static inlet pressure should not exceed 50 mb. 
The boilers are for use with NATURAL GAS ONLY.

FLUE  REQUIREMENTS

Open flue, induced draught and fan diluted systems may be used 

but must comply with the following basic requirements:

1.

  A draught diverter MUST NOT be fitted.

2.

  A draught stabiliser MUST be fitted to all types of flue systems 

and set to control the draught in the casing between neutral and 

0.2 mbar (0.08 in.w.g.) irrespective of flue height or number of 

modules firing. (see Figs. 6 and 7 for further guidance).

3.

  ALL flue systems must be insulated and/or lined and impervious  

to acid condensate. Prefabricated chimneys must have a 'U' 
value of no greater than 1.4 W/m

2 o

C at 540

 o

C (0.25 Btu/h ft

0

F at 1000

o

F).

4.

  Drainage must be provided at the base of the chimney or liner. 

(All boiler casings have a condensate drain point - see Fig. 17)

5.

  For fan diluted or induced draught systems, air flow/pressure 

switches MUST be fitted to protect against fan failure. Switches 

should be set to open if the air flow reduces by more than 15%.

900

(352)

500

(19

1

/

2

)

25(1)

500

(19

1

/

2

)

GENERAL

GENERAL

Summary of Contents for SUPER PLUS 200/S

Page 1: ...n be assured conform to the safety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of litera...

Page 2: ...Plus Installation and Servicing CAUTION To avoid the possibility of injury during the installation servicing or cleaning of this appliance care should be taken when handling edges of sheet steel comp...

Page 3: ...tment products which must be used in accordance with the manufacturers instructions For further information contact Fernox Fry Technology UK Tandem House Marlowe Way Beddington Farm Road Croydon CRO 4...

Page 4: ...of Each Module kg 69 2 69 2 69 2 69 2 69 2 69 2 69 2 lb 152 5 152 5 152 5 152 5 152 5 152 5 152 5 Weight of Water Header kg 16 3 38 2 38 2 49 8 49 8 49 8 49 8 lb 36 84 2 84 2 109 8 109 8 109 8 109 8...

Page 5: ...f BS 5978 and will occur whenever the boiler goes from a situation of no modules firing to a situation of one module firing This includes morning start up and those occasions of low load when the last...

Page 6: ...box assembly 2 Fan motor 3 Venturi and gaskets 4 Pressure switch 5 Pressure switch test connections 6 Overheat thermostat pocket 7 Water flow elbow 8 Gas inlet flange 9 Cast iron top cover plate 10 C...

Page 7: ...ulations Failure to install appliances correctly could lead to prosecution It is in your own interest and that of safety to ensure the law is complied with In addition the installation must comply wit...

Page 8: ...er house or compartment may be used provided that specialist advice is taken and that the combustion air and ventilation requirements of the boiler is provided in line with BS 6644 In addition this bo...

Page 9: ...t comply with British Gas requirements refer P7 and IM 11 All dimensions in mm in Note The discharge from both types of system MUST not allow recirculation of combustion products into the boilerhouse...

Page 10: ...5 600 6 boilers only SUPER PLUS 600 6 Boiler shown Note On 500 5 Module 1 is blanked off All dimensions in mm in Fig 9 BOILER DIMENSIONS SUPER PLUS 300 3 400 4 boilers only Note On 300 3 Module 1 is b...

Page 11: ...connection 5 in flange connection All dimensions in mm in Fig 11 Module Arrangement Super Plus 300 3 alternative 5 in flange connection 5 in flange connection All dimensions in mm in Fig 12 Module Arr...

Page 12: ...Executive Publication PM5 A minimum static head of 1 6 m is required to overcome the boiler hydraulic resistance and give a reasonable safety margin This requirement is specific to the boiler but ins...

Page 13: ...y to comply with pump manufacturers requirements 3 The open vent height above tank water level cannot be guaranteed adequate in all circumstances and does not take into account any instantaneous chang...

Page 14: ...vated by fire sensors Terminal S2 is voltage free If no other safety devices are to be used the water flow switch should be connected across S1 and S3 If all overriding safety devices are wired in ser...

Page 15: ...by unscrewing its retaining screws Offer up the module to the casing so that the square cutout lugs on the rear end plates sit over the runners within the casing and push the module home Note Lift the...

Page 16: ...boiler must be wired into the 3 way terminal block on the lower of the 3 wiring centres PCB No 11 on the left hand side of the boiler Terminals S1 S2 S3 allow safety devices to be wired directly into...

Page 17: ...The draught stabiliser should be set to control between neutral and 0 2 mbar 0 08 in w g draught in the casing with one or all modules firing A test point is provided in the boiler casing adjacent to...

Page 18: ...on the electrical supply The fan will run for 70 seconds and then for a further 35 seconds after a variable delay as previously described but at the end of this time the ignition sequence will not sta...

Page 19: ...on the part should be replaced Check the spark gap it should be 3 5 0 5 mm Fig 18 HEAT EXCHANGER Inspect the dry side of the heat exchanger finned tubes via the burner opening using a torch and by rem...

Page 20: ...ule from the boiler as previously described and remove all fittings from the module cast iron top plate 2 Remove the 16 x M10 screws and the 9 central M8 screws which secure the cast iron top plate to...

Page 21: ...e flow elbow 2 Undo the 2 screws securing the 2 halves of the controls box and carefully lower the front half 3 Remove printed circuit board No 9B as described above 4 Pull off the 2 push on connectio...

Page 22: ...proof washers Refit the wiring centre cover and secure with the 4 screws and washers Spark Generator 1 Pull the overheat thermostat coil retaining strip and split pin from the pocket in the flow elbow...

Page 23: ...eration Flame proving Main burner Fan Pilot burner ignition can occur at any time during 4s spark ignition period 8s Spark ignition period Purge period approx 35s 4s Up to 35s Fans start in sequence w...

Page 24: ...is operating iv The pressure switch differential pressure is 5 5 mb If not check the fan impeller cast venturi pressure and suction lines burner module heat exchanger or flue for blockage or leakage v...

Page 25: ...nted Circuit Board Assembly PCB 9 44 013 241 Control Knob Bulgin 46 013 755 Control Thermostat Sensor 47 058 511 Control Termostat Potentiometer Assembly 49 134 713 Reset Switch Assembly 51 134 515 Sp...

Page 26: ...26 Super Plus Installation and Servicing NOTES...

Page 27: ...27 Super Plus Installation and Servicing NOTES...

Page 28: ...st class training courses for domestic commercial and industrial heating installers engineers and system specifiers For details of courses please ring 01482 498432 Ideal is a trademark of Ideal Boiler...

Reviews: