background image

16

Super Plus  -  

Installation and Servicing

Repeat for the other 3 studs.

Take the round blanking plate supplied and fit it into the central 

bottom module opening in the casing. Secure it using the 4 M10 

nuts and washers provided. Fit the blank flanges and gaskets to 

the return water header connection. Blank off the water flow header 

connection using the 2 in. BSP cap and close taper point supplied.
A 1" BSP cap is supplied to seal the gas header connection.

300/3 Alternative Boiler (Refer Fig.11)

The procedure to blank off the bottom RH module and the central 

bottom module must be carried out as detailed under 500/5 boiler 

and 400/4 Alternative boiler above. In addition the top right hand 

module opening in the casing must be blanked off.
First remove one of the four M10 slotted studs and backnut from 

the top right hand opening in the casing, and replace by one of the 

longer studs in the blanking kit. Screw the M8 threaded portion of 

the new stud through the cast support ring and through the hole 

in the interior support strut. Fit the M8 nut and washer from the 

back and tighten.
Repeat for the other 3 studs.

Take the round blanking plate supplied and fit it into the top right 

hand module opening in the casing. Secure it at the bottom and 

right hand sides using the M10 nuts and washers.

Secure the water flow header support bracket to the round blanking 

plate using the top and LHS fixings. Blank off the water flow header 

using  the  blank  flange  and  the  2  gaskets  supplied  (flow  water 

header, gasket, blank flange, gasket & support bracket)

A 1" BSP cap is supplied to seal the gas header connection.
Blank off the return water header connection using the 2" BSP cap 

and close the taper nipple supplied.

CONNECTING BOILERS TO THE FLUE 

SYSTEM

Details of the flue design are shown in Figs. 6 and 7.
The boiler socket and flue pipe sizes are given in Table 1.

WATER CONNECTIONS AND PRESSURES

Refer to 'Installation Requirements'

All service pipework, linking the flow and return headers, should 

be adequately supported, taking care that no strain is imposed 

upon them.
Allowance must be made for any additional service pipework 

expansion.
Provision for draining the boiler should be made at the lowest 

point in the system.

A safety valve MUST be fitted.

The valve should be set at 0.7 bar (10 lb/ in

2

) ABOVE the available 

static head of water over the boiler or design operating pressure 

of the system, whichever applies, with a maximum value of 6.7 

bar (95 lb/in

 )

If  isolating  valves  are  fitted  in  the  flow  and  return  pipes  to  the 

boiler, they must NOT isolate the boiler from the open vent, safety 

valve or cold feed.
The maximum safety valve setting is 0.7 bar (10 lb/in

2

) above the 

maximum design operating head, or pressure of the boiler - 6.0 

bar (85 lb/in

2

)

ELECTRICAL CONNECTIONS

Refer to Fig.14

The mains input to the boiler must be wired into the 3 way terminal 

block on the lower of the 3 wiring centres (PCB No. 11) on the left 

hand side of the boiler.
Terminals S1, S2 & S3 allow safety devices to be wired directly into 

the boiler. Thus the water flow switch should be wired between S1 

& S2 and other devices wired between S2 & S3 (e.g., a fan diluted 

flue switch).   Terminal S2 is voltage free.

If all safety devices are wired in series with the isolation mains 

supply then terminals S1 & S3 must be linked.
The length of the conductors between the cord anchorage and the 

terminals must be such that the current carrying conductors become 

taut before the earthing conductor, if the cable or cord slips out of 

the cord anchorage.
The live and neutral conductors for each module are disconnected 

and insulated within the wiring centre for safety purposes on leaving 

the works. These wires must be connected to the appropriate L 

and N terminal strip connections on printed circuit boards 10 and 

11 within the wiring centre (see Fig.8 to 12 and Fig. 14) for each 

module.

If a 300/3 Alternative or 400/4 Alternative boiler is fitted, the unused 

module wiring must be left disconnected to ensure the module 

multipin plug remains electrically safe.

COMMISSIONING AND TESTING

The 

Super Plus

 boiler must be commissioned and tested by a 

competent person. In the case of installations covered by the 

Current Gas Safety (Installation and Use) Regulations or Rules 

in Force, the engineer shall be Gas Safe registered.

Upon request, Ideal Boilers, will provide a quote for commissioning 

or recommissioning after servicing.

FILLING THE BOILER WITH WATER

Fill the system by admitting water at the lowest point This will ensure 

air is forced from the tubes of the heat exchangers.

WATER CIRCULATION

Switch on the pump motor and check that water is circulating and 

the pump is vented.

Check the operation of the water flow switch. It should switch off 

the electrical supply to the modules when the water flow falls to 

NO MORE THAN one third of the design water flow-rate (given 

in Table 1).

HEADER GAS TIGHTNESS & PURGING THE 

GAS LINE

Turn the module gas service cock that is furthest from the gas inlet.
Connect the manometer to the tapping point at the end of the gas 

header (PTP No.1, Fig.19)
Slacken the nut on the 1" union, connecting the module to the gas 

header, and purge the gas header by turning the mains inlet gas 

tap on until gas is smelled. Retighten the union connection (see 

also IM/2). Turn off the module gas service cock and ensure that 

all other module gas service cocks are in the OFF position.
Take note of the manometer reading and turn off the mains inlet gas 

cock. A subsequent fall in pressure, after allowing for temperature 

stabilizing, indicates a leak between the mains inlet gas and 

individual module gas service which MUST be made good. The 

mains inlet gas can then be turned on again.
In all gas soundness checks, wait for 1 minute for temperature 

stabilisation and then check for pressure drop during the next 2 

minutes.

INSTALLATION

INST

ALLA

TION

Summary of Contents for SUPER PLUS 200/S

Page 1: ...n be assured conform to the safety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of litera...

Page 2: ...Plus Installation and Servicing CAUTION To avoid the possibility of injury during the installation servicing or cleaning of this appliance care should be taken when handling edges of sheet steel comp...

Page 3: ...tment products which must be used in accordance with the manufacturers instructions For further information contact Fernox Fry Technology UK Tandem House Marlowe Way Beddington Farm Road Croydon CRO 4...

Page 4: ...of Each Module kg 69 2 69 2 69 2 69 2 69 2 69 2 69 2 lb 152 5 152 5 152 5 152 5 152 5 152 5 152 5 Weight of Water Header kg 16 3 38 2 38 2 49 8 49 8 49 8 49 8 lb 36 84 2 84 2 109 8 109 8 109 8 109 8...

Page 5: ...f BS 5978 and will occur whenever the boiler goes from a situation of no modules firing to a situation of one module firing This includes morning start up and those occasions of low load when the last...

Page 6: ...box assembly 2 Fan motor 3 Venturi and gaskets 4 Pressure switch 5 Pressure switch test connections 6 Overheat thermostat pocket 7 Water flow elbow 8 Gas inlet flange 9 Cast iron top cover plate 10 C...

Page 7: ...ulations Failure to install appliances correctly could lead to prosecution It is in your own interest and that of safety to ensure the law is complied with In addition the installation must comply wit...

Page 8: ...er house or compartment may be used provided that specialist advice is taken and that the combustion air and ventilation requirements of the boiler is provided in line with BS 6644 In addition this bo...

Page 9: ...t comply with British Gas requirements refer P7 and IM 11 All dimensions in mm in Note The discharge from both types of system MUST not allow recirculation of combustion products into the boilerhouse...

Page 10: ...5 600 6 boilers only SUPER PLUS 600 6 Boiler shown Note On 500 5 Module 1 is blanked off All dimensions in mm in Fig 9 BOILER DIMENSIONS SUPER PLUS 300 3 400 4 boilers only Note On 300 3 Module 1 is b...

Page 11: ...connection 5 in flange connection All dimensions in mm in Fig 11 Module Arrangement Super Plus 300 3 alternative 5 in flange connection 5 in flange connection All dimensions in mm in Fig 12 Module Arr...

Page 12: ...Executive Publication PM5 A minimum static head of 1 6 m is required to overcome the boiler hydraulic resistance and give a reasonable safety margin This requirement is specific to the boiler but ins...

Page 13: ...y to comply with pump manufacturers requirements 3 The open vent height above tank water level cannot be guaranteed adequate in all circumstances and does not take into account any instantaneous chang...

Page 14: ...vated by fire sensors Terminal S2 is voltage free If no other safety devices are to be used the water flow switch should be connected across S1 and S3 If all overriding safety devices are wired in ser...

Page 15: ...by unscrewing its retaining screws Offer up the module to the casing so that the square cutout lugs on the rear end plates sit over the runners within the casing and push the module home Note Lift the...

Page 16: ...boiler must be wired into the 3 way terminal block on the lower of the 3 wiring centres PCB No 11 on the left hand side of the boiler Terminals S1 S2 S3 allow safety devices to be wired directly into...

Page 17: ...The draught stabiliser should be set to control between neutral and 0 2 mbar 0 08 in w g draught in the casing with one or all modules firing A test point is provided in the boiler casing adjacent to...

Page 18: ...on the electrical supply The fan will run for 70 seconds and then for a further 35 seconds after a variable delay as previously described but at the end of this time the ignition sequence will not sta...

Page 19: ...on the part should be replaced Check the spark gap it should be 3 5 0 5 mm Fig 18 HEAT EXCHANGER Inspect the dry side of the heat exchanger finned tubes via the burner opening using a torch and by rem...

Page 20: ...ule from the boiler as previously described and remove all fittings from the module cast iron top plate 2 Remove the 16 x M10 screws and the 9 central M8 screws which secure the cast iron top plate to...

Page 21: ...e flow elbow 2 Undo the 2 screws securing the 2 halves of the controls box and carefully lower the front half 3 Remove printed circuit board No 9B as described above 4 Pull off the 2 push on connectio...

Page 22: ...proof washers Refit the wiring centre cover and secure with the 4 screws and washers Spark Generator 1 Pull the overheat thermostat coil retaining strip and split pin from the pocket in the flow elbow...

Page 23: ...eration Flame proving Main burner Fan Pilot burner ignition can occur at any time during 4s spark ignition period 8s Spark ignition period Purge period approx 35s 4s Up to 35s Fans start in sequence w...

Page 24: ...is operating iv The pressure switch differential pressure is 5 5 mb If not check the fan impeller cast venturi pressure and suction lines burner module heat exchanger or flue for blockage or leakage v...

Page 25: ...nted Circuit Board Assembly PCB 9 44 013 241 Control Knob Bulgin 46 013 755 Control Thermostat Sensor 47 058 511 Control Termostat Potentiometer Assembly 49 134 713 Reset Switch Assembly 51 134 515 Sp...

Page 26: ...26 Super Plus Installation and Servicing NOTES...

Page 27: ...27 Super Plus Installation and Servicing NOTES...

Page 28: ...st class training courses for domestic commercial and industrial heating installers engineers and system specifiers For details of courses please ring 01482 498432 Ideal is a trademark of Ideal Boiler...

Reviews: