Concord CXDi/H - 

Users

FOR SHORT PERIODS (2-3 DAYS)

1.

Turn the boiler off by pressing the On/Standby [1/0] button
and viewing "Standby...0 " on the display.

2.

Wait 5 minutes then switch off or unplug the electricity
supply to the boiler.

Note.

 

In severe weather reduce the temperature set point to 60

o

C

 but do not turn off the electricity supply and leave the

"Boiler  ON.....1".

FOR LONG PERIODS (End of the heating season)

1.

Turn the boiler off by pressing the On/Standby [1/0] button
and viewing "Standby...0" on the display.

2

. Wait 5 minutes then switch off or unplug the electricity

supply to the boiler.

3.

Remove the casing front panel. Turn off the main gas cock

SERVICING INSTRUCTIONS

These are provided to assist the service engineer.

FAULT DIAGNOSIS

In the unlikely event of a fault condition, the microprocessor
will identify the fault area and display a suitable message on
the display.

Further to these accessible features there are other features
present  in the system which the installer/service engineer
should be aware of.

HOURS RUN LOG

This feature enables the engineer to determine the workload
of the boiler.

3 FEATURES OF THE CONTROL SYSTEM - continued

PUMP OVERRUN

If the flow temperature is above 75 

0

C at the time of boiler

shutdown, the controls will maintain pump operation until
the residual heat within the appliance has been dispersed
and the flow temp is below 75

 0

C.

ANTI-CYCLE DEVICE

On any heating system, if the heating load is very low,
there is a tendency for the boiler to cycle on and off rapidly.
This is inefficient and can lead to shortened boiler life. The
high/low operating system of the 

CXDi/H

 minimises the

risk of this but, in addition, the controls prevent the boiler
from short cycling by preventing subsequent ignition within
a period of 2 minutes. When active, the display will show
"ANTI-CYCLE (Flow temp)".

4 TO LIGHT THE  BOILER CONTROLS

5 TO SHUT DOWN THE BOILER

(the groove in the square head must be at right angles
to the line of the pipe) and refit the casing panel.

Note.

If severe weather (frost) conditions are anticipated during the
period of shutdown the system must be completely drained.

TO RELIGHT THE BOILER

AFTER SHORT PERIODS (2-3 DAYS)

Switch on the electricity supply to the boiler and press the
On/Standby [1/0] button to turn the boiler ON. If necessary
adjust the temperature set point etc. as required.

AFTER LONG PERIODS

Remove the casing front panel and turn the gas cock ON.

Refit the casing front panel and follow the lighting
instructions above.

In this case, the ignition sequence should be reset by pressing
the [COPY] button.

4.

If required, adjust the programme timer temperature set
point or weather compensation (if fitted) as described in
"Using the boiler features and controls".

WARNING

.

STANDBY does 

NOT

 electrically isolate the boiler.

1.

Turn on the electricity supply. The display will initially show a
start-up code followed by:

2.

To switch the boiler on press the On/Standby [1/0]  button.
The display will show :

then change every few seconds to indicate the boiler status.
The boiler will commence its ignition sequence.

3.

The boiler should light, initially at low rate, for a period of
approximately 3 minutes before proceeding to maximum
rate. If the boiler fails to light, allow the controls to cycle until
ignition is established. If the boiler fails to light after 5
attempts the display will show:

CXDi

C O N C O R D

EXIT

COPY ENTER

YES

NO

ADV

I

II

Con 1389

Display

On/Standby button

Up/ down buttons

Summary of Contents for Concord CXDi 110

Page 1: ...USERS G U I D E User s guide to commercial central heating boilers BOILERS Concord CXDi 110 H 180 H ...

Page 2: ...SENSOR Optional extra If the optional outside sensor is fitted the control system will recognise this and automatically regulate the boiler flow temperature to changes in the external temperature If the sensor is fitted an extra status information screen will appear stating whether the device has been activated or not i e Sensor on off COMMISSIONING INSTRUCTIONS These are provided to assist the in...

Page 3: ...mises the risk of this but in addition the controls prevent the boiler from short cycling by preventing subsequent ignition within a period of 2 minutes When active the display will show ANTI CYCLE Flow temp 4 TO LIGHT THE BOILER CONTROLS 5 TO SHUT DOWN THE BOILER the groove in the square head must be at right angles to the line of the pipe and refit the casing panel Note If severe weather frost c...

Page 4: ...4 Concord CXDi H Users 6 USING THE BOILER FEATURES AND CONTROLS The diagram below shows the sequence of steps to be taken when reading the instructions on the following pages ...

Page 5: ... button will access the above options in reverse When the option required is displayed and the ENTER button pressed another set of menus will be available as discussed on the following pages PROGRAMMER TIMER The programmer has 3 time zones per day for each day of the week Each day can be programmed for the requirements of that day giving 7 programmed days or using the copy facility any number of d...

Page 6: ... it cycles between high and low operation the boiler will fall through 30 before the high rate gas valve is energised 8 USING THE BOILER FEATURES AND CONTROLS continued SET TIME DATE Enables the correct time and date to be entered The display will show a flashing day of the week as follows The correct day can be selected by use of the UP or Down button and when correct the ENTER button should be p...

Page 7: ...en energised If the boiler flow temperature is equal to or greater than 55 o C then this delay will NOT occur Notes 1 If a fault occurs with the boiler thermostat the fault display screen will show C H Sensor Fault 2 When the low rate gas valve is de energised as the temperature required has been obtained the boiler will go into an anti cycle route for 2 minutes The display will indicate anti cycl...

Page 8: ...P O Box 103 National Ave Kingston upon Hull HU5 4JN Telephone 01482 492 251 Fax 01482 448 858 Registration No London 322 137 Caradon Ideal Limited pursues a policy of continuing improvement in the design and performance of its products The right is therefore reserved to vary specification without notice ...

Reviews: