2.33 MENU OPERATION
The menu option contains a list of attributes that show the operating state of the boiler. The installer should scroll down the
menu and press enter to select the desired option.
Exit
Down
Enter
Menu
Service Contact Name
Service Phone Number
Change Service Time
Press
2.34 SETTING MAXIMUM AND MINIMUM RATES
Maximum DHW and Minimum Rate can be accessed through the menu option.
Target Fan Speed: 6800rpm
Actual Fan Speed: 6800rpm
Time remaining: 10 mins
Exit
Maximum DHW Rate
Press
The boiler will run at Maximum DHW Rate for
10mins as long as there is sufficient cooling load.
Target Fan Speed: 1400rpm
Actual Fan Speed: 1400rpm
Time remaining: 10 mins
Exit
Minimum Rate
Press
The boiler will run at Minimum Rate for 10mins.
If the return temperature is under 40°C
then the fan will run for 30s at maximum
rate before ramping down over 60s to
minimum rate.
If the return temperature is above 40°C
then the fan will ramp down over 60s to
minimum rate.
Note.
For Diverter Valve Mid Position,
press down until mid position highlighted.
35