2
Viceroy GTS -
Installation & Servicing
GENERAL
Flow
Connection
in.
3 3 3 4 4 4 4
Return
Connection
in.
3 3 3 4 4 4 4
Drain
Connection
in.
2 2 2 2 2 2 2
Maximum Operating Pressure
bar
6
6
6
6
6
6
6
Boiler
Thermostat
Setting
ºC 30-90 30-90 30-90 30-90 30-90 30-90 30-90
Safety
Thermostat
Setting
ºC
110 110 110 110 110 110 110
High / Low Setting
ºC
30-90
30-90
30-90
30-90
30-90
30-90
30-90
Nominal
Flue
mm
250 250 250 300 300 300 300
Diameter
in.
10 10 10 12 12 12 12
Boiler
Water
l
366 409 452 495 538 581 624
Content
gal 80.5 89.9 99.4 109 118.4 127.8 137.3
Boiler DRY Weight
kg
1802
2072
2238
2454
2638
2880
3057
less Burner Unit
lb
3972.5
4568
4934
5410
5816
6349.5
6739.5
Maximum m
3
/h 44.78 51.74 61.88 69.06 77.11 82.87 89.77
Gas Rate
ft
3
/h 1582 1827 2185 2439 2723 2927 3170
Maximum Flue
m
3
/s 0.279 0.322 0.386 0.429 0.479 0.515 0.558
Gas Volume
ft
3
/min 591 682 818 909 1015 1091 1182
Flue Gas CO
2
/ Temperature
% / ºC
9.5 / 220 9.5 / 220
9.5 / 220
9.5 / 220
9.5 / 220
9.5 / 220 9.5 / 220
Note
.
Fuel rates and flue gas data relate to maximum output ratings.
Gas firing data relates to the use of NATURAL GAS ONLY.
Details for the use of LPG are available on request from
Ideal
Boilers.
Natural gas consumption is calculated using a calorific value of
38.7MJ/m
3
(1038Btu/ft
3
) gross or 34.9MJ/m
3
(935Btu/ft
3
) nett at
15ºC and 1013.25mbar.
Oil rates relate to Gas Oil using a calorific value of 45.56 MJ/kg
gross or 42.69 MJ/kg nett.
Table 1 Performance Data
Boiler
GTS 8
GTS 9
GTS 10
GTS 11
GTS 12
GTS 13
GTS 14
Number of Sections
8
9
10
11
12
13
14
Maximum
kW
390 450 540 600 670 720 780
Heat Output
Btu/hx10
3
1330 1535 1842 2047 2286 2457 2661
Minimum
kW
300 390 450 540 600 670 720
Heat Output
Btu/hx10
3
1024 1330 1535 1842 2047 2286 2457
Hydraulic
mbar 31.6 49.3 75.9 84.2 104.9 127.9 161.4
Resistance at 11k
in w.g.
12.6
19.7
30.3
33.7
42.0
51.2
64.6
Hydraulic
mbar
9.6 14.9 23.0 25.5 31.7 38.7 48.8
Resistance at 20k
in w.g.
3.8
6.0
9.2
10.2
12.7
15.5
19.5
Combustion
Chamber
mbar
1.1 1.5 2.0 2.5 2.5 2.5 3.5
Resistance (at zero draught)
in w.g.
0.44
0.6
0.8
1.0
1.0
1.0
1.4
Minimum Draught at Smokehood mbar
0
0
0
0
0
0
0
Outlet (for max. output)
in w.g.
0
0
0
0
0
0
0
HEALTH & SAFETY DOCUMENT NO. 635
The electricity at work regulations, 1989
. The manufacturer's
notes must NOT be taken, in any way, as overriding statutory
obligations.
IMPORTANT
. These appliances are CE certified for safety
and performance. It is, therefore, important that no external
control devices, e.g. flue dampers, economisers etc., are
directly connected to these appliances unless covered by
these Installation and Servicing Instructions or as otherwise
recommended by
Ideal Boilers
in writing. If in doubt please
enquire.
Any direct connection of a control device not approved
by
Ideal Boilers
could invalidate the certification and the
normal appliance warranty. It could also infringe the Gas Safety
Regulations and the above regulations.
Maximum
l/h 43.08 49.76 59.51 66.42 74.17 79.71 86.35
Oil
Rate
gal/h
9.48 10.95 13.09 14.61 16.32 17.54 19.00
Maximum Flue
m
3
/s 0.252 0.290 0.348 0.387 0.432 0.465 0.503
Gas Volume
ft
3
/min
534 614 737 820 915 985
1065
Flue Gas CO
2
/ Temperature
% / ºC
13 / 220
13 / 220
13 / 220
13 / 220
13 / 220
13 / 220
13 / 220
Oil
Table 2 General Data
Gas