Maximiser SE
- Installation
14
14 FLUE TERMINATION POSITION
wall terminal positions
minimum spacing
1.
Directly below, or adjacent to, an openable
window or any other ventilation opening
300 mm
12 in
2.
Below guttering, drain pipes, or soil pipes
25 mm
1 in
3.
Below eaves
25 mm
1 in
4.
Below balconies or car port roof
25 mm
1 in
5.
Above adjacent ground, roof, or balcony level
300 mm
12 in
6.
From vertical drain pipes or soil pipes
25 mm
1 in
7.
From internal or external corners
25 mm
1 in
8.
From a surface facing the terminal
600 mm
24 in
9.
From a terminal facing the terminal
1200 mm
48 in
10.
From an opening in the car port
(eg door, window) into dwelling
1200 mm
48 in
11.
Vertically from a terminal on the same wall
1500 mm
60 in
12.
Horizontally from a terminal on the same wall
300 mm
12 in
roof terminal positions
13
. Directly below an opening, air brick, windows, etc
300 mm
12 in
14.
Below plastic/painted gutters
500 mm*
20 in
15.
Below painted surface
500 mm*
20 in
16.
Below eaves or balcony
500 mm
20 in
17.
From wall 1000 mm
*Note: may be reduced to 300mm if a shield fitted
Note: the flue must be installed in accordance with BS 5440: Part 1