Maximiser SE
- Installation
13
13 EXAMPLES OF POSSIBLE FLUE INSTALLATIONS (CONT)
Fig.14.1
roof flue system
Part No.
Resistance Pa
SE 42
SE 65
Flue diameter
80/125
100/150
80/125
100/150
100/150
Standard flue
152394
152395
34
34
37
approximate length - 1000mm
Standard flue
152394
152395
34
34
37
+ Extension pack
152400
152401
4
1.8
3.6
approximate length - 2000mm
Standard flue
152394
152395
34
34
37
+ 3 x Extension packs
152400
152401
12
5.4
10.8
approximate length - 4000mm
Standard flue
152394
152395
34
34
37
+ 6 x Extension packs
152400
152401
24
10.8
21.6
approximate length - 7000mm
Note: * The twin pipe adaptor is supplied within the standard flue pack for
connection to the boiler
152394/5
152611/2
152400/1
*
roof flue system with 2x45° elbow
Part No.
Resistance Pa
SE 42
SE 65
Flue diameter
80/125
100/150
80/125
100/150
100/150
Standard flue
152394
152395
34
34
37
+ 2 Extension packs
152400
152401
8
3.6
7.2
+ 2 x 45° elbows
152618
152619
7.4
3.6
5.4
approximate length - 3500mm
Standard flue
152394
152395
34
34
37
+ 3 x Extension packs
152400
152401
12
5.4
10.8
+ 2 x 45° elbows
152618
152619
7.4
3.6
5.4
approximate length - 4500mm
Part No.
Resistance Pa
SE 42
SE 65
Flue diameter
80/125
100/150
80/125
100/150
100/150
Standard flue
152398
152399
22
22
43.3
approximate length - right 300mm; left n/a; rear 500mm
Standard flue
152398
152399
22
22
43.3
+ Extension pack
152400
152401
4
1.8
3.6
approximate length - right 1300mm; left 1000mm; rear 1500mm
Standard flue
152398
152399
22
22
43.3
+ 3 x Extension packs
152400
152401
12
5.4
10.8
approximate length - right 3300mm; left 3000mm; rear 3500mm
Note: items * are provided with the standard flue pack
horizontal flue
152398/9
152400/1
*
*
Fig.13.4
Fig.13.5
Fig.13.6