Table 1 - General Data
To obtain the gas consumption:
a. For l/s divide heat input (kW) by C.V. of the gas (MJ/m
3
)
b. For ft
3
/h divide heat input (Btu/h) by C.V. of the gas (Btu/ft
3
)
Boiler Size
FF 350 P
FF 360 P
FF 380 P
Gas supply connection
Rc 1/2 (1/2)
Flow connection
22mm
28mm copper
copper
(FEMALE)
Return connection
22mm
28mm copper
copper
(FEMALE)
Maximum static water head
m (ft.)
30.5 (100)
Minimum static water head
m (ft.)
0.45 (1.5)
Electrical supply
230 V ~ 50 Hz Boiler power consumption; 100W
Fuse rating
External; 3A
Internal; F1A to BS.4265
Water content
litre (gal.)
3.65 (0.8)
4.65 (1.0)
Dry Weight
kg (lb)
46.6 (102.8)
52.6 (116.0)
Maximum installation weight
kg (lb)
37.4 (82.5)
43.1 (95.0)
Boiler size
Height
mm (in.)
700 (27.5)
Width
mm (in.)
380 (15.0)
Depth
mm (in.)
300 (11.8)
Flue duct diameter
mm (in.)
100 (4.0)
Boiler Size
FF 350 P
FF 360 P
FF 380 P
Boiler input
kW
18.3
21.9
29.3
(Btu/h)
(62 500)
(74 700)
(100 000)
Gas consumption
l/s (ft
3
/h)
0.20 (25.0)
0.23 (29.2)
0.30 (38.1)
Boiler output
kW
14.7
17.6
23.5
(Btu/h)
(50 000)
(60 000)
(80 000)
Burner Setting
mbar
35.9
35.8
34.8
pressure (HOT)
(in.w.g.)
(14.4)
(14.4)
(14.0)
Inlet pressure
mbar (in.w.g.)
37.0 (14.8)
Seasonal efficiency (SEDBUK)*
Band D
[82.0]%
[80.4]%
[80.4]%
Table 2 - Performance Data
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of this
appliance, care should be taken when handling edges of sheet steel components
*
The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been calculated have been certified by a notified body.
Summary of Contents for FF 350