23
Buccaneer GTE -
Installation & Servicing
INSTALLATION
4
3
buc7944
36 SETTINGS (IF DHW SENSOR OPTION FITTED)
Access to DHW pump overrun adjustment potentiometers and the
DHW load temperature limiter.
1.
Remove Screws and washers.
2.
Remove the top panel from the boiler.
3.
Loosen the top protection cover from the sides.
4.
Remove the PCB protection cover.
37 SETTING THE DHW PUMP OVERRUN AND LOAD TEMPERATURE LIMITER
Setting the DHW Pump Overrun
1.
The potentiometer on the PCB in the boiler is
used to adjust the DHW pump overrun.
The overrun can vary with an adjustment range
from 0 to 10 minutes (factory setting 4 min.)
Setting the Domestic Hot Water Load
Temperature Limiter
2.
The potentiometer on the P.C.B. in the boiler is
used to adjust the boiler temperature while
heating domestic hot water.
The load temperature setting can vary from 60
to 90
o
C (factory setting 75
o
C).
Reassembly
3.
At the end of the work, reassemble the P.C.B.
protection cover and the top panel, as for
access (Frame 36), but in the reverse order.
Note
.
Do not omit the serrated washers.
1
2
buc7945
INST
ALLA
TION
Summary of Contents for Buccaneer GTE 4
Page 1: ......
Page 38: ...38 Buccaneer GTE Installation Servicing NOTES ...
Page 39: ...39 Buccaneer GTE Installation Servicing NOTES ...