CONNECTION TO THE CHIMNEY
According to the output, the difference between the
temperature of the flue gas and the ambient temperature can
be as much as 160°C. The installer will have to respect all of
the usual precautions (dilution - piping - T for the evacuation
of condensation) in order to prevent deterioration of the
chimney.
CHIMNEY AND FLUE CONNECTIONS
Detailed recommendations, relating to the design of flues for
GAS fired applications are quoted in BS. 6644 abd British
Gas Publication No. IM 11, whilst BS. 5410 Pt. 3 similarly
applies OIL fired burners.
INSTALLATION
Buccaneer GT Range
- Installation
7
Power
Mass flow of
Temperature
Chimney
the flue gas
of the flue gas
Oil 13% CO2
Natural gas 9% CO2
min. Ø
min. H
kW
g/s
< °C
mm
m
Buccaneer GT
16-26
10.5
< 180
125
5
Buccaneer GT
26-33
13.5
< 180
125
6.5
Buccaneer GT
33-40
16.5
< 180
125
7