GENERAL
Buccaneer GT Range
- Installation
5
2
INSTALLATION OF THE BOILER
The minimum dimensions indicted on the following drawing
must be respected to ensure good access around the boiler.
Remark: To allow the inlet of the combustion air, the boiler
room must be adequately ventilated, the section and the
location of which must comply with local recommendations.
VENTILATION GENERAL
Detailed recommendations for air supply are quoted in BS.
6644. The ventilation requirements in this gas fired boiler
standard are also valid for oil fired boilers or the same heat
input.
Remark: We draw your attention to the risks of corrosion of
the boilers installed in or near to rooms in which the
atmosphere can be polluted by chloride or fluoride
substances. E.G.; industrial buildings (solvents), refrigerating
machines, etc... in these cases we cannot provide a warranty.
LEVELLING
Insert the cylinder into the hole provided in each foot of the
heating body and screw the adjustable foot into it. Level.
* Attention must be paid to the space occupied by the burner when the door is open.
Note:
(1) Adjustable feet 35mm - 45mm (2) Thickness of burner door with insulation
Boiler size (no. of sections)
3
4
5
Dimension A
545
672
799
Dimension B
471
598
725
Dimension D
330
457
584
Flow and return tappings
1
1
/
4
”
1
1
/
4
”
1
1
/
4
”
Flue outlet
125
125
125
All dimensions in millimetres unless otherwise stated