means, at least one of the signal transmission channels shall send a signal to the central-station to report the
fault within 200 seconds.
The Report IP and Contact ID services must be programmed and enabled within the Protege system.
The Protege controller is compatible with the ArmorIP Internet Monitoring Receiver. Poll Time must be set to
40 seconds and the Grace Time must be set to 20 seconds.
In the Protege system, the reporting service must be configured to 40 seconds. The following options are
required for the service selected as Report IP type:
-
The
Poll Time
must be programmed to 40 seconds. Refer to the
Report IP | General
section in the
Operator Reference Manual
-
The
Contact ID Reporting Service
must be enabled and the
Service Mode
must be configured to start
with the operating system.
-
Refer to the section
Contact ID
in the Operator Reference Manual
-
The
Report IP Service
must be enabled as the primary communication channel, the
Service Mode
must
be configured to start with the operating system, and the
Reporting Protocol
must be set to ArmorIP.
-
Refer to the section
Report IP
in the Operator Reference Manual.
-
The
Trouble Input Area
must be armed in 24h mode. Refer to the section
Trouble Inputs | Areas and Input
Types
in the Operator Reference Manual.
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a minimum
of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the sequence is
reached, an indication of the failure shall be made at the premises.
In the Protege system, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The following options are required:
-
The
Dial Attempts
option must be programmed. Refer to the section
Contact ID | Settings
in the Operator
Reference Manual.
⦁
DACT communication channel check-in time is not to exceed 24 hrs.
⦁
Trouble Zone Service Test Report
-
The
Test Report Time
must be programmed. Refer to the section
Controllers | Configuration
in the
Operator Reference Manual.
-
The
Generate Input Restore on Test Input
option must be enabled. Refer to the section
Controller |
Options
in the Operator Reference Manual.
-
The
Test Report Time is Periodic
option must be enabled. Refer to the section
Controller | Options
in the
Operator Reference Manual.
-
ArmorIP detects the reception of any invalid packet on the programmed port as a potential system
compromise attempt
. Each compromise attempt sends a notification to the receiver, and logs a
Compromise Attempt event under the Live Panel Events.
The event is sent with the following details:
◾
Account Code
as defined in the Serial Receiver settings
◾
Event Code
0x163
◾
Group Code
as defined in the Serial Receiver settings
◾
Point Code
as defined in the Serial Receiver settings
Refer to the section
Global Settings | Serial Receiver
in the ArmorIP Version 3 Internet Monitoring
Application User Manual.
For UL and ULC installations the Central Station Receiving software must have the Contact ID details as
specified, programmed for the
Compromise Attempt
event.
⦁
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
⦁
The power supply is not intended to be mounted on the exterior of vault, safe, or stockroom.
PRT-HZX16-DIN | Protege Half DIN Rail 16 Input Expander | Installation Manual
35