ULC Compliance Requirements
CAN/ULC-S304
⦁
Auto Arming
Control units that support auto arming shall provide an audible signal throughout the protected area not less
than 10 min prior to the auto arming taking place. The control unit shall allow authorized users to cancel the
auto arming sequence and transmit such cancelation to the signal receiving center with the identification of
the authorized user that canceled the action.
The following options must be enabled in the Protege system when using the Auto Arming feature. When the
defer warning time is programmed to 10 minutes, the output group will be activated 10 minutes before the
system performs the Auto Arming in the associated Area.
-
The
Defer Output or Output Group
must be programmed. Refer to the section
Areas | Outputs
in the
Operator Reference Manual for programming instructions.
-
The
Defer Warning Time
must be programmed to not less than 10 minutes. Refer to the section
Areas |
Configuration
in the Operator Reference Manual.
-
The
Defer Automatic Arming
option must be enabled. Refer to the section
Areas | Options (2)
in the
Operator Reference Manual.
⦁
Arming Signal
A bell or visual indicator used as an arming acknowledgment signal must be listed to a ULC security, signaling
or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
⦁
Double EOL Input Configuration
Only double EOL Input Configuration shall be used. Refer to the
Inputs
section of this manual and the section
Inputs | Options
in the Operator Reference Manual.
⦁
Multiplex System and Poll Time
The Protege controller is compatible with the ArmorIP Internet Monitoring Receiver. Poll Time must be set to
40 seconds and the Grace Time must be set to 20 seconds.
In the Protege system, the reporting service must be configured to 40 seconds. The following options are
required for the service selected as Report IP type:
-
The
Log Polling Message
option must be enabled. Refer to the section
Report IP | Options
in the Operator
Reference Manual.
-
The
Poll Time
must be programmed to 40 seconds. Refer to the
Report IP | General
section in the
Operator Reference Manual.
⦁
Central Station Signal Receiver
The common equipment of each signal receiving center control unit shall be limited to 1000 alarm systems.
⦁
Number of attempts
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a minimum
of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the sequence is
reached, an indication of the failure shall be made at the premises.
In the Protege system, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The
Dial Attempts
option must be programmed. Refer to the section
Contact ID |
Settings
in the Operator Reference Manual.
If the PRT-4G-USB cellular modem is being used as the secondary reporting option in the installation, the
Report IP service assigned to the cellular modem must be programmed as above.
⦁
Check-In Time
DACT communication channel check-in time is not to exceed 24 hrs.
⦁
Trouble Input Service Test Report
-
The
Test Report Time
must be programmed. Refer to the section
Controllers | Configuration
in the
Operator Reference Manual.
PRT-HZX16-DIN | Protege Half DIN Rail 16 Input Expander | Installation Manual
26