The
Generate Input Restore on Test Input
option must be enabled. Refer to the section
Controller |
Options
in the Operator Reference Manual.
-
The
Test Report Time is Periodic
option must be enabled. Refer to the section
Controller | Options
in the
Operator Reference Manual.
⦁
Primary Communication Channel
The first attempt to send a status change signal shall utilize the primary communication channel.
The Report IP and Contact ID services must be programmed and enabled within the Protege system, and the
CID service must be set as the backup service.
If the PRT-4G-USB cellular modem option is being used as the secondary reporting option in the installation,
the Report IP service assigned to the cellular modem must be configured as the backup service.
The following options are required:
-
The
Contact ID Reporting Service
must be enabled and the
Service Mode
must be configured to start
with the operating system.
-
Refer to the section
Contact ID
in the Operator Reference Manual.
-
The
Report IP Service
must be enabled as the primary communication channel and the
Service Mode
must be configured to start with the operating system. The
Reporting Protocol
must be set to ArmorIP,
and the
Backup Service
must be configured to use the Contact ID Service.
If the PRT-4G-USB cellular modem option is being used as the secondary reporting option in the
installation, the
Backup Service
must be configured to use the Report IP service assigned to the cellular
modem.
-
Refer to the section
Report IP
in the Operator Reference Manual.
-
All ULC S304 P3 applications must transmit signals simultaneously over both the primary
communications channel and the Backup Service. This will occur automatically with the above
programming.
⦁
Status Change Signal
An attempt to send a status change signal shall utilize both primary and secondary communication channels.
⦁
Local Annunciation if Signal Reporting Failure
Failure of the primary communication channel or secondary communication channel shall result in a trouble
signal being transmitted to the signal receiving center within 240 seconds of the detection of the fault. Failure
of either communication channel shall be annunciated locally within 180 seconds of the fault.
The following options must be enabled in the Protege system:
-
The
Ethernet Link Failure
trouble input must be programmed.
-
The
Trouble Input Area
must be armed. Refer to the section
Trouble Inputs | Areas and Input Types
in the
Operator Reference Manual.
-
The
Log Modem Events to Event Buffer
option must be selected in the backup reporting service.
⦁
Network and Domain Access
Neither the subscriber control unit nor the signal receiving center receiver shall be susceptible to security
breaches in general-purpose operating systems.
Network access policies should be set to restrict unauthorized network access and "spoofing" or "denial of
service" attacks.
⦁
Ethernet Connections
All ethernet network connections shall be installed within the same room as the equipment.
⦁
Encryption
For active communications channel security, encryption shall be enabled at all times.
The ArmorIP-E (UDP) protocol must be used and the Encryption Type must be set to AES-256.
The following options must be enabled for the Report IP service in the Protege system.
-
The
Reporting Protocol
must be set to ArmorIP (UDP) Encrypted. The AES key must be set as specified
by monitoring station.
-
Refer to the section
Report IP | General
in the Operator Reference Manual.
PRT-HZX16-DIN | Protege Half DIN Rail 16 Input Expander | Installation Manual
27