CAN/ULC-S559

Signal Reporting

Any fault of an active communication system shall be annunciated and recorded at the signal receiving center
within 180 s of the occurrence of the fault.

The Report IP and Contact ID services must be programmed and enabled within the Protege system. The
following options are required:

-

The

Contact ID Reporting Service

must be enabled and the

Service Mode

must be configured to start

with the operating system.

-

Refer to the section

Contact ID

in the Operator Reference Manual.

-

The

Report IP Service

must be enabled as the primary communication channel, the

Service Mode

must

be configured to start with the operating system, and the

Reporting Protocol

must be set to ArmorIP.

-

Refer to the section

Report IP

in the Operator Reference Manual.

-

The

Trouble Area

must be armed. Refer to the section

Trouble Inputs | Areas and Input Types

in the

Operator Reference Manual.

In the ArmorIP Internet Monitoring Software the

Poll Time

must be set to 40 seconds and the

Grace Time

must be set to 20 seconds. Refer to the section

Poll/Grace Time

in the ArmorIP Version 3 Internet Monitoring

Application User Manual.

Central Station Signal Receiver

The maximum number of signal transmitting units connected to any transmission channel shall conform to the
manufacturer's recommendations. The ArmorIP Receiver supports up to 10000 simultaneous connections.

Refer to the section

Internet Connections Requirements

in the ArmorIP Receiver Installation Manual for further

details.

Number of attempts

In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a minimum
of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the sequence is
reached, an indication of the failure shall be made at the premises.

In the Protege system, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The

Dialing Attempts

option must be programmed. Refer to the section

Contact

ID | Settings

in the Operator Reference Manual.

If the PRT-4G-USB cellular modem is being used as the secondary reporting option in the installation, the
Report IP service assigned to the cellular modem must be programmed as above.

Check-In Time

DACT communication channel check-in time is not to exceed 24 hrs.

Trouble Input Service Test Report

-

The

Test Report Time

must be programmed. Refer to the section

Controllers | Configuration

in the

Operator Reference Manual.

-

The

Generate Input Restore on Test Input

option must be enabled. Refer to the section

Controller |

Options

in the Operator Reference Manual.

-

The

Test Report Time is Periodic

option must be enabled. Refer to the section

Controller | Options

in the

Operator Reference Manual.

Ethernet Connections

All ethernet network connections shall be installed within the same room as the equipment.

External Wiring

All wiring extending outside of the enclosure must be protected by conduit.

Power Supply Mains Power Connection

If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.

The power supply is not intended to be mounted on the exterior of vault, safe, or stockroom.

Arming Signal

PRT-HZX16-DIN | Protege Half DIN Rail 16 Input Expander | Installation Manual

29

Summary of Contents for PRT-HZX16-DIN

Page 1: ...PRT HZX16 DIN Protege Half DIN Rail 16 Input Expander Installation Manual...

Page 2: ...chanical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Logo...

Page 3: ...ower Indicator 15 Input Indicators 16 Error Code Indication 17 Error Code Display 17 Mechanical Diagram 18 Mechanical Layout 19 Technical Specifications 20 New Zealand and Australia 21 European Standa...

Page 4: ...UL1610 34 FCC Compliance Statements 36 Industry Canada Statement 37 Disclaimer and Warranty 38 PRT HZX16 DIN Protege Half DIN Rail 16 Input Expander Installation Manual 4...

Page 5: ...be connected to the RS 485 module network Up to 250 modules can be connected to the Protege system in any combination to the network over a distance of up to 900M 3000ft Further span can be achieved...

Page 6: ...oring Station Burglar Alarm Systems CAN ULC S302 Installation and Classification of Burglar Alarm Systems for Financial and Commercial Premises Safes and Vaults CAN ULC S561 Installation and Services...

Page 7: ...per wire or wires of the appropriate gauge Earth Ground Connection The DIN rail enclosure and the DIN rail modules must be grounded to a suitable single point earth ground connection in the installati...

Page 8: ...Rail Enclosure DIN Rail Enclosure Module Network RS 485 N N NA and NB DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings The Dialer s Earth Ground Connection applie...

Page 9: ...ss for wiring It is also recommended that the module is installed in an electrical room communication equipment room secure cabinet or in an accessible area of the ceiling 1 Position the DIN rail modu...

Page 10: ...s to be observed MODULE NETWORK WIRING Recommended Belden 9842 or equivalent 24AWG twisted pair with characteristic impedance of 120ohm or CAT5e CAT6 are also supported for data transmission when usin...

Page 11: ...ltage to all devices on the RS 485 network Warning The 12V N and N communication input must be supplied from only one point Connections from more than one 12V supply may cause failure or damage to the...

Page 12: ...wire tampered in the line occurs When using the EOL resistor configuration the EOL resistor option must be enabled in the input programming so that the tamper and short states can be monitored For mo...

Page 13: ...following table details the trouble inputs that are configured in the system and the trouble type and group that they activate Input Number Description Type Group ZXxxx 01 15 Reserved None None ZXxxx...

Page 14: ...e product Refer to the Protege system controller installation manual for address programming details The controller has a set limit on the number of modules of each type that it can support When addin...

Page 15: ...e update or the identification time period expiring the module will return to normal operation Fault Indicator The fault indicator is lit any time the module is operating in non standard mode If the f...

Page 16: ...t verification of inputs without the need to view the inputs from the keypad or the Protege software State Description Constantly off Input is not programmed Constantly on red Input is in an open stat...

Page 17: ...e feature in the controller s web interface 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within th...

Page 18: ...he correct installation of the input expander Status Indicators Input Indicators Inputs 13 16 12VDC Pass Through Inputs 5 8 12VDC Input 12VDC Pass Through RS 485 Input 12VDC Pass Through Inputs 1 to 4...

Page 19: ...ntial details needed to help ensure correct installation and mounting All measurements are shown in millimeters 90 00 78 40 44 68 67 18 4 67 Screw Hole 39 20 39 20 78 40 17 55 35 40 Back Front PRT HZX...

Page 20: ...to 55 C 14 to 131 F Storage Temperature 10 to 85 C 14 to 185 F Humidity 0 93 non condensing indoor use only relative humidity Mean Time Between Failures MTBF 784 316 hours calculated using RFD 2000 UT...

Page 21: ...General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards PRT HZX16 DIN Protege Half DIN Rail 16 Input Expand...

Page 22: ...your local authority for further details of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with your national legislation For...

Page 23: ...one input for masking To comply with EN 50131 1 Do not fit more than 10 unpowered detectors per input Do not fit more than one non latching powered detector per input Do not mix unpowered detectors an...

Page 24: ...k General Product Statement The UKCA Compliance Label indicates that the supplier of the device asserts that it complies with all applicable standards PRT HZX16 DIN Protege Half DIN Rail 16 Input Expa...

Page 25: ...6 86 CAN ULC S319 EN DIN 24 EN DIN 24 ATTACK P UL ULC All cabinet installations of this type must be located inside the Protected Area Not to be mounted on the exterior of a vault safe or stockroom Al...

Page 26: ...Time The Protege controller is compatible with the ArmorIP Internet Monitoring Receiver Poll Time must be set to 40 seconds and the Grace Time must be set to 20 seconds In the Protege system the repo...

Page 27: ...vice This will occur automatically with the above programming Status Change Signal An attempt to send a status change signal shall utilize both primary and secondary communication channels Local Annun...

Page 28: ...igital subscriber line DSL modems and F Cable modems Backup Power Requirements Power for network equipment such as hubs switchers routers servers modems etc shall be backed up or powered by an uninter...

Page 29: ...ommunication a digital alarm communicator transmitter shall make a minimum of 5 and a maximum of 10 attempts Where the maximum number of attempts to complete the sequence is reached an indication of t...

Page 30: ...hat the shorts and other faults on the RS 485 line connection of the keypad will not cause the controller to malfunction Fire Areas Fire areas shall be separated from burglar areas through area partit...

Page 31: ...ort 4K7 2K2 Open Close Tamper Short 4K7 4K7 Open Close Tamper Short AUX Z1 COM COM Z2 Z3 Z4 N C T amper N CZoneContact Value2 Value1 Fire zones shall be separated from burglar zones through area parti...

Page 32: ...n Close Tamper Short 4K7 2K2 Open Close Tamper Short 4K7 4K7 Open Close Tamper Short AUX Z1 COM COM Z2 Z3 Z4 N C T amper N CZoneContact Value2 Value1 ULCcertified12VDCPower Supply 12VDC 12VDC AUX 12VD...

Page 33: ...2 Open Close Tamper Short 4K7 4K7 Open Close Tamper Short AUX Z1 COM COM Z2 Z3 Z4 N C T amper N CZoneContact Value2 Value1 ULCcertified12VDCPower Supply 12VDC 12VDC AUX 12VDC 485 485 C NC NC C 12VDC A...

Page 34: ...arming acknowledgement signal must be listed to a UL security signaling or fire standard If intended to be mounted outside it must be rated for outdoor use Exit and entry delay must not exceed 60 sec...

Page 35: ...e selected as Contact ID must have the number of attempts programmed to 5 attempts The following options are required The Dial Attempts option must be programmed Refer to the section Contact ID Settin...

Page 36: ...is device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHA...

Page 37: ...is class A digital apparatus complies with Canadian ICES 003 Cet appareil num rique de la classe A est conforme la norme NMB 003 du Canada CAN ICES 3 A NMB 3 A PRT HZX16 DIN Protege Half DIN Rail 16 I...

Page 38: ...be liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design...

Page 39: ...eserved Disclaimer Whilst every effort has been made to ensure accuracy in the representation of this product neither Integrated Control Technology Ltd nor its employees shall be liable under any circ...

Reviews: