ICT Pro Series Instruction Manual Download Page 9

 

Innovative Circuit Technology Ltd. 

Status Indicators and Alarms 

The 2 LEDs on the front panel and the Form-C alarm contacts on the back indicate 
the status of the power supply: 
 

Alarm or 

Notification 

Trigger Condition 

LOAD 

Output 

BATT 

LVD 

Red 

FAULT 

LED 

Green 

POWER 

LED 

Input AC OK, 
battery charging 

Normal operation, 
battery charging

 

Enabled 

CLOSED 

-

 

ON

 

Input AC OK, 
battery charged 

Normal operation, 
battery charged  

Enabled 

CLOSED 

ON 

AC Under-
voltage Warning

 

Triggers when Input 
Voltage drops below 
approx. 90Vac 

Enabled 

CLOSED 

ON

 

ON

 

AC Fail 

AC fails or front switch 
is off (Battery above 
LVD level) 

Battery 
power 
only 

CLOSED 

ON 

Battery Low 

(when AC Off)

 

Triggers when battery 
voltage falls below the 
LVD threshold 

OFF  

OPEN 

ON 

System Fault 

Indicates internal 
circuit fault - Clears 
when all fault 
conditions are cleared. 

Battery 
power 
only 

CLOSED 

ON 

Battery Over 
Voltage Fault 

(AC present)

 

Triggers when the 
battery voltage 
exceeds the internal 
OVP threshold for 3s 

Enabled 

OPEN 

ON 

ON 

DC Overvoltage 
Shutdown 

Triggers for output 
voltage above 

16.5/33/66VDC 

for 

1s.

 

Clears when Input 
power cycled off/on 

Battery 
power 
only 

CLOSED 

ON 

Over-
temperature 
Shutdown 

Triggers when internal 
temperature is too 
high.  Clears when 
back to normal range. 

Battery 
Power 
only 

CLOSED 

ON 

The form-C alarm contact will be triggered for any condition that lights the red 
FAULT LED, or shuts down the output of the unit. 
 
 

Summary of Contents for Pro Series

Page 1: ...upply INSTRUCTION MANUAL 855 343 001 Innovative Circuit Technology Ltd Models ICT690 12S ICT690 12SB ICT690 24S ICT690 24SB ICT690 48S ICT690 48SB ICT1190 12S ICT1190 12SB ICT1190 24S ICT1190 24SB ICT...

Page 2: ...cuit breaker Ensure battery polarity is correct before connecting Do not attempt to charge a frozen battery Handle batteries with care never short circuit battery terminals CAUTION Risk of personal in...

Page 3: ...Innovative Circuit Technology Ltd 3 Table of Contents INTRODUCTION 4 CHECK and CONFIGURE UNIT 4 INSTALLATION 6 OPERATION 7 Status Indicators and Alarms 9 PRODUCT SPECIFICATIONS 10 LIMITED WARRANTY 12...

Page 4: ...on B Remote on off control input for external control of the output Floating Form C alarm contact output supports remote monitoring of unit operation Model1 Output Voltage V Max Output Current A Conti...

Page 5: ...Pro Series unit must be protected using an outlet with a branch rated circuit breaker of 20A or lower value Connection Diagram Showing Rear Connectors and SW Switch 1 4 Configure the Output Settings A...

Page 6: ...sconnect Reconnect V Switch Settings 1 UP 0 Down x either INSTALLATION Mount the unit in a standard 19 inch equipment rack ensuring side air vents are not blocked using rack mounting screws not suppli...

Page 7: ...Connect the remote on off control or unit form C alarm contact monitoring wiring to the REMOTE connector if needed as shown in the following table Pin Number Name Function 1 Shutdown Remote output sh...

Page 8: ...able on page 5 while the output voltage will be determined by the battery state of charge and will rise to the output float voltage over time The battery will be maintained at the supply output float...

Page 9: ...l Battery power only CLOSED ON Battery Low when AC Off Triggers when battery voltage falls below the LVD threshold OFF OPEN ON System Fault Indicates internal circuit fault Clears when all fault condi...

Page 10: ...0W 690W 1200W 690W 1200W 690W Output Noise max mVrms 30 30 30 30 40 40 Input Current max at 120Vac 12A 7A 12A 7A 12A 7A LVD Threshold V Default 11 5V 11 5V 23 0V 23 0V 46 0V 46 0V LVD Reconnect V Defa...

Page 11: ...nst harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause...

Page 12: ...repair The Purchaser shall at their own risk and cost return the defective product to ICT s factory or designated repair center once an RMA is issued by ICT Return of the products to the customer afte...

Page 13: ...nce or causes external to the unit including but not limited to general environmental conditions such as rust corrosive atmospheres sustained temperatures outside the specified operating range of the...

Reviews: