On units with the optional battery back-up and LVD capability (model suffix 

“B”):

 

o

 

Choose a lead-acid battery with a float voltage rating that matches the 
Pro Series output voltage, and has an Amp-hour (Ahr) capacity rating 
greater than 3 times the max charge current setting of the power supply 
(i.e. use a 75Ahr battery or larger on a 25A charge setting) 

o

 

Connect the battery negative to the supply NEG bus bar 

o

 

Connect the battery positive to an over current protection device (fuse or 
breaker) and disconnect switch 

o

 

With the battery fuse removed or disconnect switch open connect the 
fuse or switch to the supply BAT(+) terminal 

o

 

Either the POS or NEG load lead may be connected to earth ground if 
required, but the internal LVD contactor is always connected to the 
battery positive, as shown. NOTE: Do not ground the battery POS 
terminal, as this may bypass the internal LVD relay 

 

 

Connect the remote on-off control or unit form-C alarm contact monitoring 
wiring to the REMOTE connector if needed, as shown in the following table:

 

 

 

Pin Number 

Name 

Function 

Shutdown (+) 

Remote output shutdown, positive 
(2.5-16Vdc) 

Shutdown (-) 

Remote output shutdown, return 

NC 

Alarm NC (alarm state) 

NO 

Alarm NO (alarm state) 

Common 

Alarm output common 

 

REMOTE Connector: (use 22-26AWG wire) 

 
 

Check that all connections

 to the power supply are correct and tight; re-install the 

plastic bus bar cover using the original two screws provided. 
 

Connect the AC power cord

: Plug an approved AC power cord set rated for 15A 

(120V) or 10A (230V) into the IEC type AC input connector on the back panel of the 
supply (120V cord included with unit), then plug into a grounded 3 terminal 
120Vac or 230Vac power outlet, with the front panel switch in the off position. 

OPERATION 

Switch on the unit using the front panel power switch, and observe that the front 
panel green POWER LED is lit. Verify the supply output voltage using a hand held 
digital  voltmeter.  If  a  battery  is  connected  install  the  external  fuse  and  close  the 
disconnect switch. 
 

Summary of Contents for Pro Series

Page 1: ...upply INSTRUCTION MANUAL 855 343 001 Innovative Circuit Technology Ltd Models ICT690 12S ICT690 12SB ICT690 24S ICT690 24SB ICT690 48S ICT690 48SB ICT1190 12S ICT1190 12SB ICT1190 24S ICT1190 24SB ICT...

Page 2: ...cuit breaker Ensure battery polarity is correct before connecting Do not attempt to charge a frozen battery Handle batteries with care never short circuit battery terminals CAUTION Risk of personal in...

Page 3: ...Innovative Circuit Technology Ltd 3 Table of Contents INTRODUCTION 4 CHECK and CONFIGURE UNIT 4 INSTALLATION 6 OPERATION 7 Status Indicators and Alarms 9 PRODUCT SPECIFICATIONS 10 LIMITED WARRANTY 12...

Page 4: ...on B Remote on off control input for external control of the output Floating Form C alarm contact output supports remote monitoring of unit operation Model1 Output Voltage V Max Output Current A Conti...

Page 5: ...Pro Series unit must be protected using an outlet with a branch rated circuit breaker of 20A or lower value Connection Diagram Showing Rear Connectors and SW Switch 1 4 Configure the Output Settings A...

Page 6: ...sconnect Reconnect V Switch Settings 1 UP 0 Down x either INSTALLATION Mount the unit in a standard 19 inch equipment rack ensuring side air vents are not blocked using rack mounting screws not suppli...

Page 7: ...Connect the remote on off control or unit form C alarm contact monitoring wiring to the REMOTE connector if needed as shown in the following table Pin Number Name Function 1 Shutdown Remote output sh...

Page 8: ...able on page 5 while the output voltage will be determined by the battery state of charge and will rise to the output float voltage over time The battery will be maintained at the supply output float...

Page 9: ...l Battery power only CLOSED ON Battery Low when AC Off Triggers when battery voltage falls below the LVD threshold OFF OPEN ON System Fault Indicates internal circuit fault Clears when all fault condi...

Page 10: ...0W 690W 1200W 690W 1200W 690W Output Noise max mVrms 30 30 30 30 40 40 Input Current max at 120Vac 12A 7A 12A 7A 12A 7A LVD Threshold V Default 11 5V 11 5V 23 0V 23 0V 46 0V 46 0V LVD Reconnect V Defa...

Page 11: ...nst harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause...

Page 12: ...repair The Purchaser shall at their own risk and cost return the defective product to ICT s factory or designated repair center once an RMA is issued by ICT Return of the products to the customer afte...

Page 13: ...nce or causes external to the unit including but not limited to general environmental conditions such as rust corrosive atmospheres sustained temperatures outside the specified operating range of the...

Reviews: