WARNING
Risk of serious personal injury or damage to equipment and property! Always
observe the following!
•
If a battery is used ensure the nominal battery voltage is correct for the model
of power supply, and that the battery positive is connected to the BAT positive
(+) terminal and the battery negative is connected to the NEG (-) terminal.
•
Use an appropriate dc over-current protection device such as a fuse or circuit
breaker in line with the battery connection
•
Do not tie the POS and +BAT terminals together, as this will bypass the
internal LVD circuitry
•
Make any earth Ground connection to only a single LOAD or BAT terminal if
required. Do not ground both the load and battery as this may bypass the
internal LVD circuitry
•
AC input wiring to the Pro Series unit must be protected using an outlet with a
branch rated circuit breaker of 20A or lower value
Connection Diagram (Showing Rear Connectors and SW Switch 1-4)
Configure the Output Settings:
Always switch off the unit before changing the settings or making connections.
•
Choose a lead-acid battery with a nominal voltage rating (12/24/48V) that
matches the Pro Series rated output. Note that for good battery life the
battery should have a combined Ahr capacity of at least 3 times the
maximum charge current being used. (e.g. Use a 75Ahr or larger rated
battery (3 x 25A) with a 25A max charge setting)
•
Set the max charge current to be supplied to the battery by setting SW 3,
and SW 4 on the back panel according to the following chart: (note that
actual current flow to the battery may be less than the setting, and is
determined by the battery state of charge and temperature)
Shown with battery backup/LVD, option B
Note: EARTH Ground connection may be made
to either load terminal