ICT Pro Series Instruction Manual Download Page 8

Innovative Circuit Technology Ltd.

 

On units with the battery back-up option connected switch off the ac power, and 
use a hand held digital voltmeter to verify that the battery voltage is provided to 
the output load terminal. Switch AC power back on, and verify the output supply 
voltage rises to the normal output rating as the battery charges. 
 
The  unit  can  now  be  left  operating  normally.  As  long  as  the  external  back-up 
battery voltage is greater than the low voltage disconnect (LVD) level the battery 
will be connected directly to the supply output and will instantly power the load in 
case of an AC power failure. With AC power off the battery will then gradually be 
discharged by the load. When the battery voltage drops below the LVD disconnect 
level  the  internal  relay  will  open,  preventing  the  battery  from  being  excessively 
discharged.  
 
When AC power returns the supply will close the LVD relay and charge the battery 
to  bring  the  voltage  back  up  to  the  float  voltage  level.  Battery  charge  current  is 
limited to the maximum rate determined by the charge current setting of SW 3 and 
4 (see table on page 5), while the output voltage will be determined by the battery 
state of charge, and will rise to the output float voltage over time. The battery will 
be maintained at the supply output (float) voltage level until AC power is removed. 
 
Batteries  connected  directly  to  the  supply  output  (not  using  the  LVD  option  BAT 
terminal) will be charged to the supply output voltage level with a current limited 
to the maximum supply output rating. 
 
The remote shutdown input may be used to disable the supply output by applying 
a voltage from 2.5 to 16V, and the form-C alarm contacts can be used to remotely 
monitor fault conditions per the Status Indicators and Alarms table. 

 

PARALLEL OPERATION 

Up  to  3  matching  units  without  the  optional  battery  backup  capability  may  be 
connected  in  parallel  to  power  higher  current  loads.  The  unit  with  the  highest 
output  voltage will initially  provide  most  of the  load current,  and as load current 
increases the current supplied will tend to balance between the parallel units

 

 
 
 

CAUTION 

Risk of damage to equipment! 

 

Ensure battery current supplied through the optional internal LVD contactor 
cannot exceed the current rating of the unit 

 

Do not use the internal LVD contactor for parallel applications where load 
current can exceed the maximum rating of a single unit 

 
 

Summary of Contents for Pro Series

Page 1: ...upply INSTRUCTION MANUAL 855 343 001 Innovative Circuit Technology Ltd Models ICT690 12S ICT690 12SB ICT690 24S ICT690 24SB ICT690 48S ICT690 48SB ICT1190 12S ICT1190 12SB ICT1190 24S ICT1190 24SB ICT...

Page 2: ...cuit breaker Ensure battery polarity is correct before connecting Do not attempt to charge a frozen battery Handle batteries with care never short circuit battery terminals CAUTION Risk of personal in...

Page 3: ...Innovative Circuit Technology Ltd 3 Table of Contents INTRODUCTION 4 CHECK and CONFIGURE UNIT 4 INSTALLATION 6 OPERATION 7 Status Indicators and Alarms 9 PRODUCT SPECIFICATIONS 10 LIMITED WARRANTY 12...

Page 4: ...on B Remote on off control input for external control of the output Floating Form C alarm contact output supports remote monitoring of unit operation Model1 Output Voltage V Max Output Current A Conti...

Page 5: ...Pro Series unit must be protected using an outlet with a branch rated circuit breaker of 20A or lower value Connection Diagram Showing Rear Connectors and SW Switch 1 4 Configure the Output Settings A...

Page 6: ...sconnect Reconnect V Switch Settings 1 UP 0 Down x either INSTALLATION Mount the unit in a standard 19 inch equipment rack ensuring side air vents are not blocked using rack mounting screws not suppli...

Page 7: ...Connect the remote on off control or unit form C alarm contact monitoring wiring to the REMOTE connector if needed as shown in the following table Pin Number Name Function 1 Shutdown Remote output sh...

Page 8: ...able on page 5 while the output voltage will be determined by the battery state of charge and will rise to the output float voltage over time The battery will be maintained at the supply output float...

Page 9: ...l Battery power only CLOSED ON Battery Low when AC Off Triggers when battery voltage falls below the LVD threshold OFF OPEN ON System Fault Indicates internal circuit fault Clears when all fault condi...

Page 10: ...0W 690W 1200W 690W 1200W 690W Output Noise max mVrms 30 30 30 30 40 40 Input Current max at 120Vac 12A 7A 12A 7A 12A 7A LVD Threshold V Default 11 5V 11 5V 23 0V 23 0V 46 0V 46 0V LVD Reconnect V Defa...

Page 11: ...nst harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause...

Page 12: ...repair The Purchaser shall at their own risk and cost return the defective product to ICT s factory or designated repair center once an RMA is issued by ICT Return of the products to the customer afte...

Page 13: ...nce or causes external to the unit including but not limited to general environmental conditions such as rust corrosive atmospheres sustained temperatures outside the specified operating range of the...

Reviews: