background image

 

Innovative Circuit Technology Ltd.

 

11

 

Output Voltage Control

 

Output Voltage:

 Set the DC output voltage of the ICT DIN Power supply. Set 

this to match the float voltage requirement for your external battery. 
 

Temperature Coefficient/cell:

  Automatically adjust the output voltage of 

the power supply according to the battery temperature. Configure this 
setting to match the battery manufacturers recommended compensation 
value in 

mV/°C per cell. Compensation will be disabled if this setting is set 

to 0mV. Note that the power supply must have the battery temperature 
sensor (ICT-TMP) installed on the battery for this setting to have an effect. 
 

Alarm Reporting

 

Send E-mail:

 Check this box to receive an e-mail notification when a power 

supply alarm is triggered. 
 

LVD Settings

 

Disconnect Voltage

: Set the battery disconnect voltage threshold to a level 

that will protect the battery from excessive discharge. The LVD contactor will 
open when the battery discharges to this level for at least 3s.  
 

Reconnect Voltage

: Set the battery reconnect voltage to a level at least 2.0V 

more than the disconnect voltage to prevent the LVD contactor repeatedly 
cycling on and off. This setting will be used when charging the battery from 
an external dc source (such as a solar system), otherwise once AC power 
returns the LVD contactor will automatically close so that the power supply 
can charge the battery directly. 
 

LVD Setting 

24V 

48V 

Disconnect Voltage (Default) 

22.0V 

44.0V 

Reconnect Voltage (Default) 

25.0V 

50.0V 

Table 5: Disconnect and Reconnect Voltage default settings 

 

Battery Over-Current Alarm

 

Over-Current Threshold

: Set the maximum current to be drawn from the 

battery. The Battery Over Current alarm will be triggered if this level is 
exceeded. Set the threshold to 0A to disable this alarm. 

 

Device Setup 

Use this page to configure the PDU device settings. Click on the 

Save Settings

 

button when finished to save and implement all new changes. 
 

Device Info 

 

Site Name

:  Enter a custom descriptive name for the PDU 

Model:

  Displays the ICT model number for the PDU 

Hardware

:  Displays the hardware version of the PDU 

Summary of Contents for DIN Series

Page 1: ...Innovative Circuit Technology Ltd ICT DIN SERIES POWER DISTRIBUTION UNIT INSTRUCTION MANUAL 855 353 000 Model ICT DIN PDU6...

Page 2: ...nnect power and allow to cool before removing or replacing Wiring terminals may be HOT to touch Disconnect power and allow to cool before disconnecting load wires Install unit in a restricted access l...

Page 3: ...WEB BASED INTERFACE 8 Status Control 10 Alarm Status 10 Power Supply 10 Device Setup 11 Output Setup 13 Network Setup 15 E mail Setup 19 Alarm Setup 20 User Setup 21 Maintenance 22 MOBILE WEB APP 23...

Page 4: ...d alarm input status can be monitored through Ethernet communication Fuse status is also displayed by an LED indicator located over each fuse Form C alarm contacts C NO NC are provided on the top of t...

Page 5: ...se on the front of the PDU for each output terminal block The fuse number on the front of the PDU matches the output terminal block number Consult your local electrical codes for wire ampacity and fus...

Page 6: ...Depending on the alarm circuit refer to table 2 connect it between normally open NO and common C between normally closed NC and common C or both The built in web server controls this alarm The alarm c...

Page 7: ...current is above the set value Alarm Input 1 4 Activate Alarm Form C Contact is checked Digital Alarm is triggered Output Over Current Alarm 1 6 Activate Alarm Form C Contact is checked Output Current...

Page 8: ...emote monitoring and control using any standard web browser such as Microsoft Edge Google Chrome or Mozilla Firefox To connect with your networked PDU do the following 1 Start Your Browser 2 Enter the...

Page 9: ...the various monitoring configuration and control features available through the PDU s graphical web interface To log out click on the Logout link on the top right of your browser window The system wi...

Page 10: ...er to individual outputs If the COMM port on the PDU is connected to an ICT DIN Power Supply this page will also display Power Supply status information including output voltage output current alarm s...

Page 11: ...ischarges to this level for at least 3s Reconnect Voltage Set the battery reconnect voltage to a level at least 2 0V more than the disconnect voltage to prevent the LVD contactor repeatedly cycling on...

Page 12: ...abled in sequence when the Enable All Outputs button is pressed on the Status Control page rather than enabling all outputs simultaneously This delay helps prevent power surges that can occur when too...

Page 13: ...1 to 80 minutes that the remote IP address must stop responding to ping requests from the PDU before the Network Watchdog will trigger an output power cycle Ensure this time is greater than the normal...

Page 14: ...ter the PDU starts up after a power failure or reset Ignore Fuse Status Will mask the fuse open circuit detection to prevent false alarms on unused channels Enable Power Cycling Check this box to enab...

Page 15: ...least 5s will trigger the Over Current Alarm Disable this alarm by setting the threshold to 0A Activate Form C Contact Checking this box will cause the Alarm relay to trigger for an over current condi...

Page 16: ...DU The following ports may be changed within a range of 1 to 65565 if required HTTP Port This port is used for HTTP traffic between the PDU and your browser The default HTTP port is 80 and if you chan...

Page 17: ...through SNMP If this box is unchecked all information available from the SNMP agent will be read only SNMP Control Access Sets the level of device control that is allowed through SNMP This setting is...

Page 18: ...or the selected SNMP version will need to be configured Trap Community Assign the community string password that will be sent with all SNMPv1 traps Some trap receivers are able to filter based on Trap...

Page 19: ...es that are to receive all e mail notifications from the PDU Use commas to separate multiple addresses This field can also be used to send a text message notification to a phone see the Text Message A...

Page 20: ...otification to be sent when an output fuse is blown Note that the e mail settings must be fully configured on the E mail Setup page for this to occur System Under Voltage Alarm Under Voltage Threshold...

Page 21: ...front PDU alarm messages Contact Type Select if the external alarm contact input is to be used and what contact type is connected to each input Choose Normally Open contact Normally Closed contact or...

Page 22: ...gs Maintenance Use this page to reset the PDU soft reset restore the PDU default settings or send a test e mail to verify e mail functionality Reset Distribution Panel Clicking the Reset button will r...

Page 23: ...Ping Diagnostics Tool Use this feature to verify connectivity of any network connected device Enter the hostname or IP address of the target device and then click the Ping button MOBILE WEB APP Use t...

Page 24: ...the standard User password and other settings are not affected 1 Press and hold the recessed reset button on the front panel for approximately 10 seconds 2 Release the button 3 Log in to the unit as u...

Page 25: ...rt you must change the HTTP port the PDU uses from 80 to something else such as 8000 Valid port numbers are in the range of 1 to 65535 See the Network Setup section for information on assigning new ne...

Page 26: ...port 8000 Figure 7 PDU Access With Router Address TEXT MESSAGE ALARM NOTIFICATIONS The PDU can send alarm notifications as text messages to a cell phone by configuring the alarm e mails to be sent to...

Page 27: ...section See the Password Reset section for details on how to reset the port number to the factory default value If your network switch allows you to manually configure port speed and duplex settings...

Page 28: ...d outputs does not exceed the system current rating NOTE Most fuses should be continuously operated at no more than 80 of their nominal current rating Consult the fuse manufacturers specifications Pow...

Page 29: ...Innovative Circuit Technology Ltd 29 Warranty 2 years Dimensions L x W x H 4 4 x 5 3 x 5 7 111mm x 134mm x 144mm Figure 8 Mechanical Dimensions...

Page 30: ...such damage Product that is returned as defective which is determined to operate within published specifications will be returned to the Purchaser freight collect ICT assigns to Purchaser any warranti...

Reviews: