UDP Port
: Enter a UDP port within the range of 1 to 65565 to be used for
applying firmware upgrades to the inverter. The default UDP port is
9393
.
SNMP:
Configure these settings if you would like to use SNMP based monitoring. SNMP
(Simple Network Management Protocol) is an industry standard protocol for
network management software. Enabling the SNMP function on the inverter will
allow standard SNMP management software to connect to the SNMP agent
running on the inverter and read real time system information such as battery
voltage, and output power. The inverter can send SNMP traps to the external
management software when an alarm or fault occurs.
The information available from the SNMP agent is described in a MIB
(Management Information Base) file, which can be downloaded from the
inverter’s
Help
page. The unique inverter MIB file must then be imported into your external
SNMP management software.
Enable SNMP
: Check this box to enable the SNMP agent.
Read Community
: Enter the community string/password for read-only SNMP
access. The default read community string is “public”.
Trap Community
: Enter the community string/password that will be sent with
all traps. Some trap receivers are able to filter based on Trap Community. The
default trap community string is “public”.
Trap IP Addresses
: Enter the IP address for up to two devices that will receive
SNMP traps from the inverter.
Enable SNMP Write Access
: Check this box to allow remote SNMP control of
the inverter output. If this box is unchecked information from the unit will be
read-only.
Write Community
: Enter the community string/password for read-write SNMP
access. The default write community is “write”.
NOTE:
The community strings should be changed to unique passwords before enabling
SNMP as the defaults are well known.
SNMP Contact Information
: Enter contact information such as an operator
name and phone number for the inverter, which can be read via SNMP
queries. This information is optional.