5. Setting up the device
5.1. Switching on
Once the installation is complete, start the device by applying the voltage supply. Before, check
once again that all electrical connections are correct.
Starting sequence
For 1 second during the switching-on process, the segment test (
8 8 8 8 8
) is displayed
followed by an indication of the software type and, after that, also for 1 second the software
version. After the starting sequence, the device switches to operation/display mode.
5.2. Standard parameterisation:
(Flat operation level)
To parameterize the display, press the
[P]
-key in operating mode for 1 second. The display
then changes to the menu level with the first menu item
TYPE
.
5. Setting up the device
Menu level
Parameterisation level
Type of temperature metering,
Default:
The temperature can be displayed in
°
C or in
°
F. Confirm the selection with
[P]
and the display switches back to menu level.
Setting the decimal point,
:
Default:
The decimal point on the display and the physical unit can be changed with
[▲]
[▼]
. If e.g. temperature measurement in
°
C is selected, then choose between 0
°
C
and 0.0
°
C in the parameterisation level. Confirm with
[P]
, the display then
switches back to the menu level again.
Setting the measuring range start / offset value,
:
Default:
The value for the sensor calibration is selectable from the smallest to the highest
digit with
[▲][▼]
and confirmed with
[P]
. After the last digit the display switches
back to the menu level again. The value calibration for a temperature
measurement in
°
C can be adjusted between -20.0 and +20.0 and in
°
F between -
36.0 and +36.0. If the type of the measurement is changed later, then the value is
rounded.