5. Setting up the device
Menu level
Parameterisation level
Setting the display time,
:
Default:
The display time is set with
[▲] [▼]
. The display moves up in increments of 0.1
up to 1 second and in increments of 1.0 to 10.0 seconds. Confirm the selection by
pressing the
[P]
button. The display then switches back to the menu level again.
Selection of analog output,
Default:
Three output signals are available: 0-10 VDC, 0-20 mA and 4-20 mA, with this
function, the demanded signal is selected.
Setting up the final value of the analog output,
Default:
The final value is adjusted from the smallest digit to the highest digit with
[▲] [▼]
and digit by digit confirmed with
[P]
. A minus sign can only be parameterised on
the highest digit. After the last digit, the device changes back into menu level.
Setting up the initial value of the analog output,
Default:
The final value is adjusted from the smallest digit to the highest digit with
[▲] [▼]
and digit by digit confirmed with
[P]
. A minus sign can only be parameterised on
the highest digit. After the last digit, the device changes back into menu level.
Threshold values / limits,
Default:
This value defines the threshold, that activates/deactivates an alarm.
then