5. Setting up the device
Menu level
Parameterisation level
Selection of analog output,
Default:
Available are 3 output signals: 0-10 VDC, 0-20 mA and 4-20 mA, with this function, the
demanded signal is selected.
Setting up the final value of the analog output,
Default:
The final value is adjusted from the smallest digit to the highest digit with
[▲] [▼]
and digit by
digit confirmed with
[P]
. A minus sign can only be parameterised on the highest digit. After the
last digit, the device changes back into menu level.
Setting up the initial value of the analog output,
Default:
The initial value is adjusted from the smallest digit to the highest digit with
[▲] [▼]
and digit by
digit confirmed with
[P]
. A minus sign can only be parameterised on the highest digit. After the
last digit, the device changes back into menu level.
Threshold values / limits,
Default:
This value defines the threshold, that activates/deactivates an alarm.
Hysteresis for limit values,
Default:
The delayed reaction of the alarm is the difference to the threshold value, which is defined by
the hysteresis.
Function for threshold value undercut / exceedance,
Default:
A limit value undercut is selected with
(for LOW = lower limit value), a limit value
exceedance with
(for HIGH = higher limit value). If e.g. limit value 1 is on a threshold level
of 100 and allocated with function
, an alarm is activated by reaching the threshold level. If
the threshold value was allocated to
an alarm will be activated by undercutting the
threshold value, as long as the hysteresis is zero.